DSP Components
445
© 2017, ATEÏS, member of PAX ProAV Group
Play Times: Set the time of [Message Group] (max.100 times).
Note: The play times of [Message Group] is based on with the order of Prev>Norma>Post.
Idle Time: Set the Idle Time between the former and latter [Message Groups] (max.100 seconds).
Interrupt: Allow the interruption during the playback. If not, the message in Message Group will be
ended after the Fire Alarm stops.
Renew: Allow to recalculate the play times in [Message Group]. During the playback of [Message
Group], this setting shall be referred to whether to be recalculated or continued the current play
times once the status of EVAC Input has changed.
Behavior: Set the playback mode of message when the status of EVAC Input has changed. There
are three types of modes including [Continue Play], [Restart Play] and [Net Time Continue Play].
o
Continue Play: Continually play the message when changing to another paging zone.
o
Restart Play: Start playing over again from Prev when changing to another paging zone.
o
Next Time Continue Play: Start playing after the playing list of [Message Group] ends.
Active: Select to active the message playback of Prev/Post.
Note: This button needs to be selected if users intend to make adjustment of [Message Play
List].
Prev/Post/Normal Message: There are three types of Message Play for [Message Group]: Prev/
Post/Normal.
Note: Before clicking [Prev/Post] button, make sure the [Active] button is selected forwards.
o
Prev/Post Message: Edit the lists of playback messages in [Message Group] from top to
bottom orderly. See the picture as below.
For more information of Message Play Component, please read
o
Normal Message: After playing the Prev Message from [Message Group], the messages with
high signal of EVAC Input will be played in order. When the playbacks of [Prev Message] end,
the [Post Message] will play afterwards. In the use of [Normal Message], the EVAC Input must
be fully connected to.
o
See the picture below which lists the [EVAC Input Channel] of each device. To use the EVAC
Channels, select [Active] button, then click [...] Message button for further message setting.