Error was judged as no connection between the ceiling cassette panel into Indoor PCB
communication (feedback signal).
Possible Causes
1. Indoor unit ceiling cassette panel connector was not properly / wrongly connected into the PCB connector
2. Air swing motor (inside the panel) was locked (jammed) or no operation
=> Check the air swing motor shaft can be rotate with hand
3. Air swing motor (inside the panel) wiring connector loosen or wire broken
=> Check the air swing motor wire connector connection
4. Indoor PCB for air swing control was malfunction
=> Check with multi meter at pin 1(red)-2, 1-3, 1-4 & 1-5 : 12Vdc
=> Check with multi meter at pin 6 (red)-7, 6-8, 6-9 & 6-10 : 12Vdc
=> Check with multi meter at pin 11 (red)-12, 11-13, 11-14 & 11-15 : 12Vdc
=> Check with multi meter at pin 16 (red)-17, 16-18, 16-19 & 16-20 : 12Vdc
WRONG
insertion
position
Panel
Connector
Panel
Connector
CORRECT
insertion
position
P09 Error description : Indoor unit ceiling cassette air swing motor do not operate
SM830283-00_欧州向け R32シングル36-71形TD&SM.indb 18
2020/01/29 21:17:49
Содержание S-3650PF3E
Страница 20: ...19 MEMO SM830283 00_欧州向け R32シングル36 71形TD SM indb 19 2020 01 29 21 46 03 ...
Страница 178: ... MEMO 1 13 5 SM830283 00_欧州向け R32シングル36 71形TD SM indb 5 20 01 30 10 26 09 ...
Страница 198: ... MEMO 2 4 1 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 2020 01 29 19 52 20 ...
Страница 204: ... MEMO 3 2 1 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 20 01 28 11 25 46 ...
Страница 270: ... MEMO 5 4 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 2020 01 29 21 17 57 ...
Страница 272: ... MEMO 6 1 SM830283 00_欧州向け R32シングル36 71形TD SM indb 1 20 01 20 10 15 08 ...
Страница 294: ... MEMO 7 21 SM830283 00_欧州向け R32シングル36 71形TD SM indb 21 20 01 28 11 22 25 ...
Страница 321: ...202001 SM830283 00_欧州向け R32シングル36 71形TD SM indb 1 20 01 23 9 32 11 ...