1
1-11-1-2-9
Unit no.
After completing the address setting under the Section
“8. TEST RUN”, carry out the following procedure.
1. Keep pressing the
,
and
simultaneously for 4 or more seconds.
The “Maintenance func” screen appears on the LCD
display.
2. Press the
or
button to see each menu.
If you wish to see the next screen instantly,
press the or
button.
Select “8. Detailed settings” on the LCD display and
press the
button.
The “Detailed settings” screen appears on the LCD
display.
Select the “Unit no.” by pressing the or
button for changes.
3. Select the “Code no.” by pressing the or
button.
Change the “Code no.” to “3F” by pressing
the
or
button (or keeping it pressed).
4. Select the “Set data” by pressing the or
7. Select the “Unit no.” by pressing the or
5. Select the “Code no.” by pressing the or
button.
Change the “Code no.” to “06” by pressing the
or button (or keeping it pressed).
button.
(“0007” or “0000” set at shipment) Change the Setting
Data “0001” by pressing the
or
button.
Then press the
button.
button and press the
button.
The “Exit detailed settings and restart?”
(Detailed setting-end) screen appears on the LCD
display.
Select “YES” and press the
button.
buttons
How to make drain pump ineffective and changing
heating intake temperature
Operating the High-spec Wired Remote Controller
(CZ-RTC5B)
20:30 (THU)
[ ] START
Maintenance func
Sel.
Page [
] Confirm
20:30 (THU)
1. Outdoor unit error data
2. Service contact
3. RC setting mode
4. Test run
Maintenance func
Sel.
20:30 (THU)
5. Sensor info.
6. Servicing check
7. Simple settings
8. Detailed settings
Page [
] Confirm
Detailed settings
Unit no.
Code no.
Set data
1-1
10
0005
Sel.
Next
20:30 (THU)
Detailed settings
Unit no.
Code no.
Set data
0007
1-1
Sel.
Next
20:30 (THU)
3F
Detailed settings
Unit no.
Code no.
Set data
1-1
06
0004
20:30 (THU)
Sel.
Next
6. Select the “Set data” by pressing the or
button. (“0004” set at shipment)
Change the Setting Data “0000” by pressing the
or
button.
Then press the
button.
Detailed settings
Code no.
Set data
ALL
20:30 (THU)
Sel.
Next
01
0002
E
and restart?
NO
YES
xit detailed settings
SM830283-00_欧州向け R32シングル36-71形TD&SM.indb 9
20/01/30 10:25:48
Содержание S-3650PF3E
Страница 20: ...19 MEMO SM830283 00_欧州向け R32シングル36 71形TD SM indb 19 2020 01 29 21 46 03 ...
Страница 178: ... MEMO 1 13 5 SM830283 00_欧州向け R32シングル36 71形TD SM indb 5 20 01 30 10 26 09 ...
Страница 198: ... MEMO 2 4 1 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 2020 01 29 19 52 20 ...
Страница 204: ... MEMO 3 2 1 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 20 01 28 11 25 46 ...
Страница 270: ... MEMO 5 4 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 2020 01 29 21 17 57 ...
Страница 272: ... MEMO 6 1 SM830283 00_欧州向け R32シングル36 71形TD SM indb 1 20 01 20 10 15 08 ...
Страница 294: ... MEMO 7 21 SM830283 00_欧州向け R32シングル36 71形TD SM indb 21 20 01 28 11 22 25 ...
Страница 321: ...202001 SM830283 00_欧州向け R32シングル36 71形TD SM indb 1 20 01 23 9 32 11 ...