1
1-11-2-1-8
The refrigerant (R32), which is used in the air conditioner, is a flammable refrigerant. So the
Check of Density Limit
[Type U3]
requirements for installation space of appliance are determined according to the refrigerant
charge amount [m
c
] used in the appliance.
Regarding the refrigerant charge amount [m
c
] used in the appliance, refer to the installation
instructions for the outdoor unit.
The minimum indoor floor space compared with the amount of refrigerant is roughly as follows:
0.0
5.0
10.0
15.0
20.0
25.0
30.0
35.0
40.0
45.0
0
.
0
5
.
0
0
.
1
5
.
1
0
.
2
3.0
4.0
2.5
3.5
5.0
5.5
6.0
6.5
7.0
7.5
8.0
8.5
4.5
1.22
7.90
Can not be installed
Fig. 1-11-2-1-1
Can be installed
[m
c
] : the refrigerant charge amount (k )
[Amin]
: minimum indoor floor space (m
2
)
[m
c
] : The refrigerant charge amount (k ) (Total of refrigerant at shipment and refrigerant
charge amount in the field).
[Amin] : Minimum indoor floor space (m
2
)
[m
c
]
[Amin]
1.22
2.5
1.3
2.6
1.4
2.8
1.5
3.0
1.6
3.2
1.7
3.4
1.8
3.6
SM830283-00_欧州向け R32シングル36-71形TD&SM.indb 8
20/01/30 10:25:59
Содержание S-3650PF3E
Страница 20: ...19 MEMO SM830283 00_欧州向け R32シングル36 71形TD SM indb 19 2020 01 29 21 46 03 ...
Страница 178: ... MEMO 1 13 5 SM830283 00_欧州向け R32シングル36 71形TD SM indb 5 20 01 30 10 26 09 ...
Страница 198: ... MEMO 2 4 1 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 2020 01 29 19 52 20 ...
Страница 204: ... MEMO 3 2 1 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 20 01 28 11 25 46 ...
Страница 270: ... MEMO 5 4 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 2020 01 29 21 17 57 ...
Страница 272: ... MEMO 6 1 SM830283 00_欧州向け R32シングル36 71形TD SM indb 1 20 01 20 10 15 08 ...
Страница 294: ... MEMO 7 21 SM830283 00_欧州向け R32シングル36 71形TD SM indb 21 20 01 28 11 22 25 ...
Страница 321: ...202001 SM830283 00_欧州向け R32シングル36 71形TD SM indb 1 20 01 23 9 32 11 ...