General Precautions on Wiring
NOTE
*
With ring-type wire terminal.
Check the type of the outdoor unit terminal board
as illustrated below and make connection.
Recommended Wire Length and Wire Diameter for Power Supply System
2. Type F3
S-3650PF3E, S-6071PF3E
The remote control wiring and the inter-unit control wiring should be wired apart from the inter-unit power wiring.
Use shielded wires for inter-unit control wiring between units and ground the shield on both sides.
(1) Before wiring, confirm the rated voltage of the unit as shown on its nameplate, then carry out the wiring closely following the
wiring diagram.
WARNING
(2) This equipment is strongly recommended to be installed with Earth Leakage Circuit Breaker (ELCB) or Residual Current
Device (RCD). Otherwise, it may cause electrical shock and fire in case of equipment breakdown or insulation breakdown.
Earth Leakage Circuit Breaker (ELCB) must be incorporated in the fixed wiring in accordance with the wiring regulations.
The Earth Leakage Circuit Breaker (ELCB) must be an approved circuit capacity, having a contact separation in all poles.
(3) To prevent possible hazards from insulation failure, the unit must be grounded.
(4) Each wiring connection must be done in accordance with the wiring system diagram.
Wrong wiring may cause the unit to misoperate or become damaged.
(5) Do not allow wiring to touch the refrigerant tubing, compressor, or any moving parts of the fan.
(6) Unauthorized changes in the internal wiring can be very dangerous. The manufacturer will accept no responsibility for any
damage or misoperation that occurs as a result of such unauthorized changes.
(7) Regulations on wire diameters differ from locality to locality. For field wiring rules, please refer to your LOCAL ELECTRICAL
CODES before beginning.
You must ensure that installation complies with all relevant rules and regulations.
(8) To prevent malfunction of the air conditioner caused by electrical noise, care must be taken when wiring as
follows:
CAUTION
Check local electrical codes and regulations before wiring. Also, check any specified instruction or
limitations.
Control wiring
(D) Remote control wiring
(C) Inter-unit (between Integrated
control system and indoor units)
control wiring
(E) Remote control wiring for group
control
0.75 mm
2
0.75 mm
2
(AWG #18)
Use shielded wiring*
(AWG #18)
0.75 mm
2
(AWG #18)
Max. 1,000 m
(D) + (E) : Max. 500 m (E) : Max. 200 m
The above descriptions can be used for the model CZ-RTC4 or CZ-RTC5B. For
other remote controllers, refer to the manual of each unit.
Indoor unit
(Type of 3-line connection [1, 2 and 3] with indoor and outdoor units)
Type
Connection cable between outdoor and indoor unit
1.5 mm
2
F3
Max. 40 m
L
N
1
2
3
Connection cable between
outdoor and indoor unit
Power supply cable
If 1, 2 and 3 are shown on the terminal
board, it is for 3-line connection.
(F) Outdoor unit U-36 ~ 71PZ3E5
SM830283-00_欧州向け R32シングル36-71形TD&SM.indb 1
20/01/30 10:24:57
Содержание S-3650PF3E
Страница 20: ...19 MEMO SM830283 00_欧州向け R32シングル36 71形TD SM indb 19 2020 01 29 21 46 03 ...
Страница 178: ... MEMO 1 13 5 SM830283 00_欧州向け R32シングル36 71形TD SM indb 5 20 01 30 10 26 09 ...
Страница 198: ... MEMO 2 4 1 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 2020 01 29 19 52 20 ...
Страница 204: ... MEMO 3 2 1 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 20 01 28 11 25 46 ...
Страница 270: ... MEMO 5 4 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 2020 01 29 21 17 57 ...
Страница 272: ... MEMO 6 1 SM830283 00_欧州向け R32シングル36 71形TD SM indb 1 20 01 20 10 15 08 ...
Страница 294: ... MEMO 7 21 SM830283 00_欧州向け R32シングル36 71形TD SM indb 21 20 01 28 11 22 25 ...
Страница 321: ...202001 SM830283 00_欧州向け R32シングル36 71形TD SM indb 1 20 01 23 9 32 11 ...