1.
How to set the external static pressure
buttons
Keep pressing the
,
and
simultaneously for 4 or more seconds.
The “Maintenance func” screen appears on the LCD
display.
2. Press the
or
button to see each menu.
If you wish to see the next screen instantly, press the
or
button.
Select “8. Detailed settings” on the LCD display and press
the
button.
The “Detailed settings” screen appears on the LCD display.
or
Select the “Unit no.” by pressing the
button for changes.
3. Select the “Code no.” by pressing the
or
or
button.
Change the “Code no.” to “B0” by pressing the
button (or keeping it pressed).
4. Select the “Set data” by pressing the
or
Then press the
Table 1-7-2 Setting the external static pressure
button.
button.
Select one of the “Set data” among “0001” – “0010”
according to the desired external static pressure setting by
pressing the
or
button.
Then press the
button.
(See the table below.)
When setting to auto airflow volume control:
Select the setting data to “-002”.
5. Select the “Unit no.” by pressing the
or
button and press the
button.
The “Exit detailed settings and restart?” (Detailed setting-
end) screen appears on the LCD display.
Select “YES” and press the
button.
When the setting is completed, perform the test run for the
external static pressure setting described in “Auto External
Static Pressure Setting Operation”.
Code no.
Unit no.
20:30 (THU)
[ ] START
Maintenance func
Sel.
20:30 (THU)
1. Outdoor unit error data
2. Service contact
3. RC setting mode
4. Test run
Page [
] Confirm
Maintenance func
Sel.
20:30 (THU)
5. Sensor info.
6. Servicing check
7. Simple settings
8. Detailed settings
Page [
] Confirm
Detailed settings
Unit no.
Code no.
Set data
1-1
0001
Sel.
Next
20:30 (THU)
B0
Detailed settings
Set data
10
0001
1-1
Sel.
Next
20:30 (THU)
xit de
ings
E
and restart?
tailed sett
NO
YES
Detailed settings
Unit no.
Code no.
Set data
1-1
10
0001
20:30 (THU)
Sel.
Next
Indoor unit type
Item code
3650
6071
B0
Outdoor unit type
–
150
0010
140
External static pressure of the rated
airfl
ow volume (Pa)
0009
130
0008
120
0007
110
0006
90
0005
70
0004
50
0003
30 *
0002
10
0001
No auto airfl
ow volume setting
-001
-002
A
uto airfl
ow volume setting
* Setting at shipment
SM830283-00_欧州向け R32シングル36-71形TD&SM.indb 3
20/01/30 10:24:48
Содержание S-3650PF3E
Страница 20: ...19 MEMO SM830283 00_欧州向け R32シングル36 71形TD SM indb 19 2020 01 29 21 46 03 ...
Страница 178: ... MEMO 1 13 5 SM830283 00_欧州向け R32シングル36 71形TD SM indb 5 20 01 30 10 26 09 ...
Страница 198: ... MEMO 2 4 1 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 2020 01 29 19 52 20 ...
Страница 204: ... MEMO 3 2 1 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 20 01 28 11 25 46 ...
Страница 270: ... MEMO 5 4 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 2020 01 29 21 17 57 ...
Страница 272: ... MEMO 6 1 SM830283 00_欧州向け R32シングル36 71形TD SM indb 1 20 01 20 10 15 08 ...
Страница 294: ... MEMO 7 21 SM830283 00_欧州向け R32シングル36 71形TD SM indb 21 20 01 28 11 22 25 ...
Страница 321: ...202001 SM830283 00_欧州向け R32シングル36 71形TD SM indb 1 20 01 23 9 32 11 ...