4-19
4 4
•
Causes and corrections in instances when auto address setting cannot be started.
•
Causes and corrections in instances when auto address setting starts, but cannot be completed successfully.
•
If alarm E15, E16, or E20 appears after auto address setting is started, check the following items.
Trouble
Trouble
Cause and correction
Cause and correction
Check the "Alarm Displays" table and
correct the problem.
An alarm appears on the remote controller sometime from several
seconds to several minutes after auto address setting is started.
Check that the remote controller wiring
and the inter-unit control wiring are
connected correctly.
Check that the indoor unit power is ON.
Check the "Alarm Displays" table and
correct the problem.
E15
E16
The total capacity of indoor units is too lower than that of outdoor unit.
The total capacity of indoor units is too higher than that of outdoor unit.
Alarm description
Alarm display
4-15. Self-Diagnostics Function Table
An alarm appears immediately when auto address setting is started
from the remote controller.
Nothing happens when the operator attempts to start auto address
setting from the remote controller.
SM830283-00_欧州向け R32シングル36-71形TD&SM.indb 19
2020/01/30 13:58:50
Содержание S-3650PF3E
Страница 20: ...19 MEMO SM830283 00_欧州向け R32シングル36 71形TD SM indb 19 2020 01 29 21 46 03 ...
Страница 178: ... MEMO 1 13 5 SM830283 00_欧州向け R32シングル36 71形TD SM indb 5 20 01 30 10 26 09 ...
Страница 198: ... MEMO 2 4 1 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 2020 01 29 19 52 20 ...
Страница 204: ... MEMO 3 2 1 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 20 01 28 11 25 46 ...
Страница 270: ... MEMO 5 4 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 2020 01 29 21 17 57 ...
Страница 272: ... MEMO 6 1 SM830283 00_欧州向け R32シングル36 71形TD SM indb 1 20 01 20 10 15 08 ...
Страница 294: ... MEMO 7 21 SM830283 00_欧州向け R32シングル36 71形TD SM indb 21 20 01 28 11 22 25 ...
Страница 321: ...202001 SM830283 00_欧州向け R32シングル36 71形TD SM indb 1 20 01 23 9 32 11 ...