1
1-11-1-2-27
Work List
No.
Content
Check
□
Possibility of Failure & Checkpoint
Installation
1
Are the indoor units installed following the
content of the section " SELECTING
THE INSTALLATION SITE"?
(on page 1-11-1-2-1)
□
There is a possibility of light injure or loss of
property.
Tubing &
Wiring
4
Is the earth leakage circuit breaker
(all-pole switching function provided)
installed?
□
Power failure or short circuit may cause electric
shoc
k or fir
e. Check installation work and ground
wire work.
5 Is there any wrong installation of optional
parts or wrong wiring?
□
6 Was the ground wire work performed?
□
7
Are there any wrong power supply wiring,
wrong connection wire, wrong signal wire
or loose screw?
□
8 Is the thickness of wire in accordance with
rule?
□
9 Is the power-supply voltage equal to the
nameplate of the unit?
□
10
Was the check of the air
tight test, flared
tube fitting and gas leakage on the
welded portion performed?
□
If the gas leakage occurs, the unit quality not only
becomes inferior but affects environment. Repair it
as quickly as possible.
Drain
Check
11
Has the adhesive been applied to the
drain connecting portion (resin portion) of
the indoor unit?
□
The resin portion cracks after a few months and it
may cause water drain.
12 Is there water leakage?
□
Since there is a possibility of water drain, repair the
drain pipe if the drain failure or water drain occurs.
13
Indoor unit drain pipe has a downward
gradient (1/100 or more) by rule. Is the
drain w
ater fl
owing smoothly?
□
Heat
Insulation
14
Was the heat insulation work at a suitable
location including the flared tube fitting
(refrigerant tube & drain pipe) performed
properly?
□
The quality of unit not only becomes inferior but
there is a possibility of the water drain. So, perform
the heat insulation work properly.
Test Run
15 Did the abnormal sound occur?
□
Check if there is a fan contact or distortion of the
indoor unit.
16 Did the cool and war
m airfl
ow discharge
from the indoor unit?
□
Check if the unit does not operate or there is a
wrong tubing or wiring connection with another
system.
CHECKLIST AFTER INSTALLATION WORK
SM830283-00_欧州向け R32シングル36-71形TD&SM.indb 27
20/01/30 10:25:55
Содержание S-3650PF3E
Страница 20: ...19 MEMO SM830283 00_欧州向け R32シングル36 71形TD SM indb 19 2020 01 29 21 46 03 ...
Страница 178: ... MEMO 1 13 5 SM830283 00_欧州向け R32シングル36 71形TD SM indb 5 20 01 30 10 26 09 ...
Страница 198: ... MEMO 2 4 1 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 2020 01 29 19 52 20 ...
Страница 204: ... MEMO 3 2 1 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 20 01 28 11 25 46 ...
Страница 270: ... MEMO 5 4 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 2020 01 29 21 17 57 ...
Страница 272: ... MEMO 6 1 SM830283 00_欧州向け R32シングル36 71形TD SM indb 1 20 01 20 10 15 08 ...
Страница 294: ... MEMO 7 21 SM830283 00_欧州向け R32シングル36 71形TD SM indb 21 20 01 28 11 22 25 ...
Страница 321: ...202001 SM830283 00_欧州向け R32シングル36 71形TD SM indb 1 20 01 23 9 32 11 ...