Operating the Timer Remote Controller
(CZ-RTC4)
Setting Item Code “
”
1. Press and hold down the
,
and
simultaneously for 4 or more seconds.
buttons
(
blink on the LCD display.)
, the Unit No., Item Code and Detailed Data will
2. The indoor unit numbers in the group control will be
3.
4.
5. Press the
button.
The display will stop blinking and remain illuminated.
6. Press the
button. The fan motor will stop operating
and the LCD display will return to the normal stop mode.
sequentially displayed whenever the Unit Select button is
pressed
.
Only the fan motor for the selected indoor unit will operate
during this time.
Specify the “
” item code by pressing the
/
buttons for the temperature setting buttons
and confirm the values.
(“
” set at shipment )
Press the
/
buttons for the time to amend the
values for the set data.
See Table 1-11-1-2-3 and Fig. 1-11-1-2-2 and select a
value between “
” and “
”.
Select “
” if the auto airflow volume setting is
activated.
1. Press and hold down the
button for 4 or more seconds.
“
Auto Airflow Volume Control Operations and External
Static Pressure Setting-Check Operation
” will be displayed on the LCD display.
2. Press the
button to start the test run.
3. Select the operation mode
(Fan) by pressing the
A
by pressing the
(Mode select) button.
d
e
e
p
s
n
a
f
e
h
t
t
c
e
l
e
s
n
e
h
T
(Fan speed) button.
4.
NOTE
Auto airflow volume control operations and external static
pressure setting-check operations will not be performed
unless the above settings are made.
5.
Table 1-11-1-2-3 Setting the external static pressure
The fan motor will be activated and auto airflow volume
control operations or external static pressure setting-check
operations will be started.
The power of the airflow will change while these operations
are in progress.
The external static pressure setting-check operations and
auto airflow volume control operations will be completed in
about 3 to 30 minutes.
“
” display will be disappeared from the LCD display.
Press the
button to halt the test run.
airfl
ow and condensation.
*
Failure to set this parameter may result in decreased
A
3
1, 6
4
5
1
2
A
°
°
1
3
2, 5
Indoor unit type
Item code
3650
6071
Outdoor unit type
–
150
External static pressure of the rated
airfl
ow volume (Pa)
140
130
120
110
90
70
50
30 *
10
No auto airfl
ow volume setting
A
uto airfl
ow volume setting
SM830283-00_欧州向け R32シングル36-71形TD&SM.indb 17
20/01/30 10:25:52
Содержание S-3650PF3E
Страница 20: ...19 MEMO SM830283 00_欧州向け R32シングル36 71形TD SM indb 19 2020 01 29 21 46 03 ...
Страница 178: ... MEMO 1 13 5 SM830283 00_欧州向け R32シングル36 71形TD SM indb 5 20 01 30 10 26 09 ...
Страница 198: ... MEMO 2 4 1 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 2020 01 29 19 52 20 ...
Страница 204: ... MEMO 3 2 1 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 20 01 28 11 25 46 ...
Страница 270: ... MEMO 5 4 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 2020 01 29 21 17 57 ...
Страница 272: ... MEMO 6 1 SM830283 00_欧州向け R32シングル36 71形TD SM indb 1 20 01 20 10 15 08 ...
Страница 294: ... MEMO 7 21 SM830283 00_欧州向け R32シングル36 71形TD SM indb 21 20 01 28 11 22 25 ...
Страница 321: ...202001 SM830283 00_欧州向け R32シングル36 71形TD SM indb 1 20 01 23 9 32 11 ...