Checking the Drainage
Be careful since the fan will start
when you short the pin on the
indoor unit control PCB.
After wi
1-10.
ring (see
ELECTRICAL WIRING) and drain
piping are completed, use the following procedure to check
that the water will drain smoothly. For this, prepare a bucket
and wiping cloth to catch and wipe up spilled water.
(1) Connect power to the power terminal board (L/1, N/2
terminals) inside the electrical component box.
(2) Slowly pour about 1 L of water into the drain pan to
check drainage.
●
Important Note for Wiring 4-Way Cassette Type
(3) Short the check pin (CHK) (6P : 1-4) on the indoor
unit control PCB and operate the drain pump. Check the
.
water flow through the transparent drain pipe and see if
there is any leakage.
* If the check pin (CHK) (6P:1-4) is shorted, the fan starts
rotating at high speed and could cause injury.
(4) When the check of drainage is complete, open the check
pin (CHK) (6P : 1-4) and remount the tube cover.
(5) Checkpoint after installation
After installation of indoor and outdoor units, panels
and electrical wiring, check the section “ CHECKLIST
(1) The power supply inlet is located at the lower area of
the refrigerant tubing side of the unit. The electrical
component box is located at the air intake of the bottom
of the unit.
(2) Before installing the panel for cassette, be sure to carry
out the wiring connection.
(3) Remove the lid located on the bottom of the indoor unit
attaching the electrical component box by unscrewing
screws (M4 × L6) (×2).
Power supply inlet
(4) Lead the wires from the power supply inlet to the unit.
Be sure to lead the wires through the power supply inlet.
Make sure that no wire is caught between the indoor unit
and panel for cassette. Otherwise, the unit may cause a
fire.
(5) Connect the wires into the terminals through the power
supply inlet for the electrical component box.
Fix the wires with a clamping clip.
(6) Reinstall the lid of the electrical component box in its
original position with paying attention not to have the
wires caught in the lid.
See “
ELECTRICAL WIRING”.
CAUTION
Over 100 mm
Plastic container
for water intake
Drain pan outlet
Water (Approx. 1 L)
Drainage check
Screws (M4 × L6) position
AFTER INSTALLATION WORK” on page 1-11-1-1-29.
1-10.
SM830283-00_欧州向け R32シングル36-71形TD&SM.indb 6
20/01/30 10:25:05
Содержание S-3650PF3E
Страница 20: ...19 MEMO SM830283 00_欧州向け R32シングル36 71形TD SM indb 19 2020 01 29 21 46 03 ...
Страница 178: ... MEMO 1 13 5 SM830283 00_欧州向け R32シングル36 71形TD SM indb 5 20 01 30 10 26 09 ...
Страница 198: ... MEMO 2 4 1 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 2020 01 29 19 52 20 ...
Страница 204: ... MEMO 3 2 1 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 20 01 28 11 25 46 ...
Страница 270: ... MEMO 5 4 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 2020 01 29 21 17 57 ...
Страница 272: ... MEMO 6 1 SM830283 00_欧州向け R32シングル36 71形TD SM indb 1 20 01 20 10 15 08 ...
Страница 294: ... MEMO 7 21 SM830283 00_欧州向け R32シングル36 71形TD SM indb 21 20 01 28 11 22 25 ...
Страница 321: ...202001 SM830283 00_欧州向け R32シングル36 71形TD SM indb 1 20 01 23 9 32 11 ...