4-15
4 4
T10 (CN061):
4-13. Indoor Unit Control PCB Switches and Functions
[Indoor unit control PCB]
6P plug (YEL)
/ Used for remote control operation. (See the Remote Control Section.)
Control items: (1) Start/stop input
(3) Start signal output
EXCT (CN073):
(2) Remote controller prohibit input
(4) Alarm signal output
DISP (CN062):
CHK (CN062):
JP1 (JP001):
Fan drive (CN032): 2P plug (WHT)
/ This terminal sends the signal to the ventilation fan when a commercially
Power LED:
EEPROM (IC010):
2P plug (RED)
/ Can be used for demand control. When input is present, forces the unit to
operate with the thermostat OFF.
6P plug (BLK)
2-5Pin / Short-circuiting this Pin allows operation to be controlled by the remote
controller even when an outdoor unit is not connected. (In this case, alarm “E04,” which
indicates trouble in the serial communication between the indoor and outdoor unit, does not
occur.)
6P plug (BLK)
1-4Pin / Test Pin. Short-circuiting this Pin allows the indoor FM (H fan speed),
drain pump
, flap motor (F1 position), and electronic
expansion valve full-open position to be
checked.
However this function turns OFF if the indoor unit protection mechanism is activated.
The components will operate even if the remote controller and outdoor unit are not
connected, however the remote control cannot be used for control even if it is connected.
This Pin can be used for short-term tests.
Jumper wire
/ Allows selection of the T10 terminal start/stop signal. (See the Remote
Control Section.)
Setting at time of shipment: Pulse signal
Jumper wire cut: Static signal (continuous signal)
available ventilation fan is operated by the FAN button on the wired remote controller. (See
the Remote Control Section.)
Use a ventilation fan which can accept the no-voltage contact A signal as the external input
signal.
LED (RED)
/ Illuminates when the power is ON. Flashes when there is trouble with the
EEPROM (IC010: nonvolatile memory).
Nonvolatile memory
/ Used to store model information and other data. When replacing
the PCB, remove the EEPROM from the old PCB and install it onto the new PCB. If there is
IC trouble, replace with a new IC (provided with the servicing PCB), and set the necessary
information using the wired remote controller. (For the setting procedure, see the servicing
technical materials.)
Type U3, Type F3
L
N
1
2
3
Connection cable between
outdoor and indoor unit
Power supply cable
■
■
JP001
EXCT (CN073)
FAN DRIVE (CN032)
EEPROM (IC010)
DISP
CHK (CN062)
T10 (CN061)
ACXA73-3129* : 4-Way Cassette Type (Type U3) Indoor Unit Control Board
ACXA73-3440* : Middle Static Pressure Duct Type (Type F3) Indoor Unit Control Board
OPTION (CN060)
POWER LED (D002)
RC
JP001
EXCT (CN073)
FAN DRIVE (CN032)
EEPROM (IC010)
DISP
CHK (CN062)
T10 (CN061)
OPTION (CN060)
POWER LED (D002)
RC
SM830283-00_欧州向け R32シングル36-71形TD&SM.indb 15
2020/01/30 13:58:48
Содержание S-3650PF3E
Страница 20: ...19 MEMO SM830283 00_欧州向け R32シングル36 71形TD SM indb 19 2020 01 29 21 46 03 ...
Страница 178: ... MEMO 1 13 5 SM830283 00_欧州向け R32シングル36 71形TD SM indb 5 20 01 30 10 26 09 ...
Страница 198: ... MEMO 2 4 1 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 2020 01 29 19 52 20 ...
Страница 204: ... MEMO 3 2 1 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 20 01 28 11 25 46 ...
Страница 270: ... MEMO 5 4 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 2020 01 29 21 17 57 ...
Страница 272: ... MEMO 6 1 SM830283 00_欧州向け R32シングル36 71形TD SM indb 1 20 01 20 10 15 08 ...
Страница 294: ... MEMO 7 21 SM830283 00_欧州向け R32シングル36 71形TD SM indb 21 20 01 28 11 22 25 ...
Страница 321: ...202001 SM830283 00_欧州向け R32シングル36 71形TD SM indb 1 20 01 23 9 32 11 ...