4. Mini VRF System Alarm Codes
E02 Remote Controller Transmission Error
Error Detection Method
Error Diagnosis
When the remote controller itself cannot transmit. Or when it cannot receive the signal it transmitted itself, or when they are
different and judged an error.
Malfunction of the remote controller itself (transmit circuit error)
•
1.
2.
2
2-2
2-4
Is the wireless remote controller connected to on the indoor unit’s
control PC board?
Is the indoor unit under group control?
1-1
Are the wires 1 (white) & 2 (black) to the remote control group
shorted or opened?
1-2
2-1
Disconnect the connector mentioned above on the board of the
indoor unit control PC board, and see whether the E02 goes off after
several minutes. (When doing so, if two remote controllers are
being used and the wireless remote controller is the main remote
controller, set the other remote controller as the main.)
2-2
1-2
2-1
Correct the wiring
2-1
2-3
2-4
Yes
Yes
Yes
No
No
No
Replace wireless remote control parts including wiring.
2-3
Is there a short, miswiring, open, wrong contact or grounding
in the remote control’s wiring?
2-4
Correct the wiring
Replace the indoor
unit’s control PC
board
Yes
No
Group
Control
Wiring
1 Remote
Control
Group
Wiring
Yes
No
Regarding the remote controller check, refer to the Reference Materials.
•
For information on the procedures for replacing the nonvolatile memory (EEPROM) of the indoor unit and/or replacing the
indoor unit’s control board, refer to the manual that is packaged with the indoor unit service board.
•
5
- 11
5
4. Mini VRF System Alarm Codes
Mini VRF SYSTEM
Trouble Diagnosis
2
Power on
1-3
Is the central control unit’s powered off?
Is the central control unit connected?
1-1
1-2
Replace wireless remote control parts including wiring.
Is there a short, miswiring, open, wrong contact or grounding
in the remote control’s wiring?
3-3
3-4
Disconnect the connector mentioned above on the control PC board
of the indoor unit control PC board, and see whether the E03 goes off
after several minutes. (When doing so, if two remote controllers are
being used and the wireless remote controller is the main remote
controller, set the other remote controller as the main.)
3-2
Are all the Main/Sub switches on the connected central control unit
set to Sub?
1-3
Is the indoor/outdoor operations line connected to the central
control unit opened?
1-5
2-2
3-1
Is the indoor unit under group control?
2-1
Correct the setting
3-1
Are the wires 1 (white) & 2 (black) to the remote control group
opened, have wrong contact or grounded?
2-2
3-2
1-2
2-1
1-4
1-5
Correct the setting
2-1
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
No 3-4
Correct the wiring
Yes
No Replace the indoor
unit control board
3-3
Yes
No 3-4
Is the wireless remote controller connected to on the indoor unit’s
control PC board?
3-1
Of the central control units that are connected, set only the uppermost central control unit to
Main and the others to Sub. The order from top to bottom is communication adaptor
→ system controller → ON/OFF controller.
1-4
Remote
controller
3 Indoor
unit
control
PC board
1 Central
control unit
E03 Error in Indoor Unit Receiving Signal from Remote Controller (central)
Error Detection Method
(When indoor unit(s) are connected)
Error Diagnosis
It is judged an error when there is no communication from any remote controller (collectively) in a 3-minute period or if there
is no communication from the central device in a 15-minute period.
When there was once communication, but during use the remote control wiring is opened or miswired.
The line to the central control unit for indoor/outdoor operations is opened.
The power to the central control unit is not on and remote controllers are not being used (or the indoor/outdoor operations
line to the central control unit is opened).
When remote controller are not being used, only the sub remote controller is set up.
•
•
•
•
1.
2.
Settings are made only for sub remote controller.
•
ON
1 2 3 4 5 6 7
7
8
ON
1 2 3 4
4
5 6 7 8
ON Side
OFF Side
ON Side
OFF Side
Main: OFF Side
Sub: ON Side
Central Control Main/Sub Switch
Main: OFF Side
Sub: ON Side
Central Control Main/Sub Switch
System Controller
ON/OFF Controller
SW1
Regarding the remote controller check, refer to the Reference Materials.
•
For information on the procedures for replacing the nonvolatile memory (EEPROM) of the indoor unit and/or replacing the
indoor unit’s control board, refer to the manual that is packaged with the indoor unit service board.
•
SM830283-00_欧州向け R32シングル36-71形TD&SM.indb 6
2020/01/29 21:17:43
Содержание S-3650PF3E
Страница 20: ...19 MEMO SM830283 00_欧州向け R32シングル36 71形TD SM indb 19 2020 01 29 21 46 03 ...
Страница 178: ... MEMO 1 13 5 SM830283 00_欧州向け R32シングル36 71形TD SM indb 5 20 01 30 10 26 09 ...
Страница 198: ... MEMO 2 4 1 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 2020 01 29 19 52 20 ...
Страница 204: ... MEMO 3 2 1 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 20 01 28 11 25 46 ...
Страница 270: ... MEMO 5 4 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 2020 01 29 21 17 57 ...
Страница 272: ... MEMO 6 1 SM830283 00_欧州向け R32シングル36 71形TD SM indb 1 20 01 20 10 15 08 ...
Страница 294: ... MEMO 7 21 SM830283 00_欧州向け R32シングル36 71形TD SM indb 21 20 01 28 11 22 25 ...
Страница 321: ...202001 SM830283 00_欧州向け R32シングル36 71形TD SM indb 1 20 01 23 9 32 11 ...