1. U-36PZ3E5, U-50PZ3E5, U-60PZ3E5, U-71PZ3E5
Outdoor Unit
WARNING
The appliance shall be stored, installed and operated in a well ventilated room with indoor
fl
oor area larger than
A
min
(m²) [refer to Check of Density Limit] and without any continuously operating ignition source. Keep away from open
fl
ames, any operating gas appliances or any operating electric heater. Else, it may explode and cause injury or death.
The mixing of different refrigerants within a system is prohibited. Models that use refrigerant R32 and R410A have a
different charging port thread diameter to prevent erroneous charging with refrigerant R22 and for safety.
Therefore, check beforehand. [The charging port thread diameter for R32 and R410A is 12.7 mm (1/2 inch).]
Ensure that foreign matter (oil, water, etc.) does not enter the piping.
Also, when storing the piping, securely seal the opening by pinching, taping, etc. (Handling of R32 is similar to R410A.)
Operation, maintenance, repairing and refrigerant recovery should be carried out by trained and certi
fi
ed personnel in
the use of
fl
ammable refrigerants and as recommended by the manufacturer. Any personnel conducting an operation,
servicing or maintenance on a system or associated parts of the equipment should be trained and certi
fi
ed.
Any part of refrigerating circuit (evaporators, air coolers, AHU, condensers or liquid receivers) or piping should not be
located in the proximity of heat sources, open
fl
ames, operating gas appliance or an operating electric heater.
The user/owner or their authorized representative shall regularly check the alarms, mechanical ventilation and detectors,
at least once a year, where as required by national regulations, to ensure their correct functioning.
A logbook shall be maintained. The results of these checks shall be recorded in the logbook.
In case of ventilations in occupied spaces shall be checked to con
fi
rm no obstruction.
Before a new refrigerating system is put into service, the person responsible for placing the system in operation should
ensure that trained and certi
fi
ed operating personnel are instructed on the basis of the instruction manual about the
construction, supervision, operation and maintenance of the refrigerating system, as well as the safety measures to be
observed, and the properties and handling of the refrigerant used.
The general requirement of trained and certifi
ed personnel are indicated as below:
a)
Knowledge of legislation, regulations and standards relating to fl
ammable refrigerants; and,
b)
Detailed knowledge of and skills in handling
fl
ammable refrigerants, personal protective equipment, refrigerant
leakage prevention, handling of cylinders, charging, leak detection, recovery and disposal; and,
c)
Able to understand and to apply in practice the requirements in the national legislation, regulations and Standards; and,
d)
Continuously undergo regular and further training to maintain this expertise.
Air-conditioner piping in the occupied space shall be installed in such a way to protect against accidental damage in
operation and service.
Precautions shall be taken to avoid excessive vibration or pulsation to refrigerating piping.
Ensure protection devices, refrigerating piping and
fi
ttings are well protected against adverse environmental effects
(such as the danger of water collecting and freezing in relief pipes or the accumulation of dirt and debris).
Expansion and contraction of long runs piping in refrigerating systems shall be designed and installed securely (mounted
and guarded) to minimize the likelihood hydraulic shock damaging the system.
Protect the refrigerating system from accidental rupture due to moving furniture or reconstruction activities.
To ensure no leaking,
fi
eld-made refrigerant joints indoors shall be tightness tested. The test method shall have a
sensitivity of 5 grams per year of refrigerant or better under a pressure of at least 0,25 times the maximum allowable
pressure (>1.04MPa, max 4.15MPa). No leak shall be detected.
SM830283-00_欧州向け R32シングル36-71形TD&SM.indb 1
20/01/30 10:25:57
Содержание S-3650PF3E
Страница 20: ...19 MEMO SM830283 00_欧州向け R32シングル36 71形TD SM indb 19 2020 01 29 21 46 03 ...
Страница 178: ... MEMO 1 13 5 SM830283 00_欧州向け R32シングル36 71形TD SM indb 5 20 01 30 10 26 09 ...
Страница 198: ... MEMO 2 4 1 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 2020 01 29 19 52 20 ...
Страница 204: ... MEMO 3 2 1 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 20 01 28 11 25 46 ...
Страница 270: ... MEMO 5 4 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 2020 01 29 21 17 57 ...
Страница 272: ... MEMO 6 1 SM830283 00_欧州向け R32シングル36 71形TD SM indb 1 20 01 20 10 15 08 ...
Страница 294: ... MEMO 7 21 SM830283 00_欧州向け R32シングル36 71形TD SM indb 21 20 01 28 11 22 25 ...
Страница 321: ...202001 SM830283 00_欧州向け R32シングル36 71形TD SM indb 1 20 01 23 9 32 11 ...