5-2-1-16
5
2
Remove the short
2-1
Are the CHK pin, TEST pin and DISP pin on the indoor unit control
PC board short-circuited?
Is the indoor unit powered off?
1-1
1-2
3-4
Is the remote control group’s wiring opened?
2-1
Is the wiring of the remote control group wired according to the
wiring diagram?
2-3
Run the auto address setting again.
2-4
Run the auto address setting again after correcting the wiring of the remote control group.
2-5
Power on
1-2
Correct the wiring
2-2
2-4
2-5
Yes
Yes
Yes
Yes
No
No
No
2-3
3-1
Yes
No
No
Check the group settings (Item Code 14) from the remote control’s
detailed settings mode. Is the main remote controller (1) set to more
than one remote controller or to separate (0)?
2-2
Substitute
Sub
Remote
Controller
3
1 Indoor Unit
E18 Faulty Communication in Group Control Wiring
Error Detection Method
Error Diagnosis
When the main remote controller cannot communicate with a sub remote controller in the remote control group.
It is judged an error if a sub remote controller in a remote control group fails to communicate with the main remote controller
for a period of three minutes.
An indoor unit within the control group does not have its power on.
The CHK pin and TEXT pin on the indoor unit in the control group are shorted.
Remote control group wiring is opened.
More than one indoor unit in the control group is set to Main.
An indoor unit in the control group is set to Separate.
•
•
•
•
•
The DISP pin of an indoor unit sub remote controller in the control group is shorted.
•
1.
2.
Replace wireless remote control parts including wiring.
Replace the indoor unit control PC board.
3-3
Is the wireless remote controller connected to on the indoor unit’s
control PC board?
3-1
Disconnect the connector mentioned above on the control PC board
of the indoor unit control PC board, and see whether the E18 goes off
after several minutes. (When doing so, if two remote controllers are
being used and the wireless remote controller is the main remote
controller, set the other remote controller as the main.)
3-2
Yes 3-2
3-4
No
3-3
3-4
Yes
No
Indoor
unit
control
PCB
For information on the remote control’s detailed settings, refer to the Reference Materials.
•
For information on the procedures for replacing the Indoor unit control PCB, refer to the manual that is packaged with the
indoor unit service board.
•
SM830283-00_欧州向け R32シングル36-71形TD&SM.indb 16
2020/01/29 21:17:48
Содержание S-3650PF3E
Страница 20: ...19 MEMO SM830283 00_欧州向け R32シングル36 71形TD SM indb 19 2020 01 29 21 46 03 ...
Страница 178: ... MEMO 1 13 5 SM830283 00_欧州向け R32シングル36 71形TD SM indb 5 20 01 30 10 26 09 ...
Страница 198: ... MEMO 2 4 1 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 2020 01 29 19 52 20 ...
Страница 204: ... MEMO 3 2 1 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 20 01 28 11 25 46 ...
Страница 270: ... MEMO 5 4 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 2020 01 29 21 17 57 ...