1
1-11-1-1-10
●
Finishing the Installation
After finishing insulating and taping over the tubing, use sealing
putty to seal off the hole in the wall to prevent rain and draft
from entering.
Apply putty here
Tubing
HOW TO INSTALL THE TIMER REMOTE
CONTROLLER OR HIGH-SPEC WIRED
REMOTE CONTROLLER (OPTIONAL PART)
NOTE
See “Section 2. TEST RUN”.
●
Accessories Supplied with Unit
(4-Way Cassette)
Part Name
Figure
Q’ty
Remarks
Full-scale
installation
diagram
1 Printed on
container box
Washer
8 For suspension
bolts
Screw
4 For full-scale
installation diagram
Insulating tape
2 For gas and liquid
tube flare nuts
Flare insulator
1 For liquid tube
Flare insulator
1 For gas tube
Drain hose
1
Hose band
1 For securing drain
hose
Part Name
Figure
Q’ty
Remarks
Packing
1
Drain insulator
1
Clamper
4 For electrical wiring
Operating
Instructions
1
Installation
Instructions
1
● Use M10 for suspension bolts.
● Field supply for suspension bolts and nuts.
●
Type of Copper Tube and Insulation Material
If you wish to purchase these materials separately from a local
source, you will need:
1. Deoxidized annealed copper tube for refrigerant tubing.
2. Foamed polyethylene insulation for copper tubes as
required to precise length of tubing. Wall thickness of the
insulation should be not less than 8 mm.
3. Use insulated copper wire for field wiring. Wire size varies
with the total length of wiring. See the section
“1-10. ELECTRICAL WIRING” for details.
CAUTION
Check local electrical codes and regulations before
obtaining wire. Also, check any specified instructions or
limitations.
Additional Materials Required for Installation
1. Refrigeration (armored) tape
2. Insulated staples or clamps for connecting wire (See your
local codes.)
3. Putty
4. Refrigeration tubing lubricant
5. Clamps or saddles to secure refrigerant tubing
6. Scale for weighing
As f
or S-6071PU3E, the
following
accessories are additionally provided.
Part Name
Figure
Q’ty
Remarks
Different-
diameter-tube
joint
1
1
Gas so
cket tube A :
ø15.88
→ ø12.7
Insulating
tape
Liquid so
cket tube B :
ø9.52
→
ø6.35
2
For gas and liquid
tube flare nuts
SM830283-00_欧州向け R32シングル36-71形TD&SM.indb 10
20/01/30 10:25:07
Содержание S-3650PF3E
Страница 20: ...19 MEMO SM830283 00_欧州向け R32シングル36 71形TD SM indb 19 2020 01 29 21 46 03 ...
Страница 178: ... MEMO 1 13 5 SM830283 00_欧州向け R32シングル36 71形TD SM indb 5 20 01 30 10 26 09 ...
Страница 198: ... MEMO 2 4 1 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 2020 01 29 19 52 20 ...
Страница 204: ... MEMO 3 2 1 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 20 01 28 11 25 46 ...
Страница 270: ... MEMO 5 4 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 2020 01 29 21 17 57 ...
Страница 272: ... MEMO 6 1 SM830283 00_欧州向け R32シングル36 71形TD SM indb 1 20 01 20 10 15 08 ...
Страница 294: ... MEMO 7 21 SM830283 00_欧州向け R32シングル36 71形TD SM indb 21 20 01 28 11 22 25 ...
Страница 321: ...202001 SM830283 00_欧州向け R32シングル36 71形TD SM indb 1 20 01 23 9 32 11 ...