1-1-1-1-3
1
1
Single - Type
1-1. Unit Specifications
PZ3
1. 4-Way Cassette Type S-6071PU3E(60) / U-60PZ3E5
INDOOR
MODEL
S-6071PU3E(60)
-
-
PANEL
MODEL
Standard type : CZ-KPU3 or CZ-KPU3W / ECONAVI type : CZ-KPU3A or CZ-KPU3AW
-
-
OUTDOOR
MODEL
-
U-60PZ3E5
-
Branch pipe
MODEL
-
Performance test condition
ISO5151 / EN14511 / EN12102 / EN14825
Power supply
Ø, Hz
1Ø 50Hz
1Ø 50Hz
V
220V
230V
240V
220V
230V
240V
Min
Max
C
O
O
L
I
N
G
Capacity
kW
6.0
6.0
6.0
-
-
-
2.0
7.1
BTU/h
20500
20500
20500
-
-
-
6800
24200
Current
A
-
-
-
7.45
7.15
6.85
-
-
Input power
W
-
-
-
-
-
-
-
-
TOTAL W
-
1.610k
1.610k
1.610k
0.290k
2.360k
Annual consumption
TOTAL kWh *
4
-
-
-
-
805
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.73
3.73 / A
3.73
6.90
3.01
ErP
*
6
Pdesign
kW
-
-
-
-
6.0
-
-
-
SEER
(W/W)
-
-
-
-
7.8
-
-
-
Annual consumption
kWh
-
-
-
-
269
-
-
-
Class
-
-
-
-
A++
-
-
-
Power factor
%
-
-
-
98
98
98
-
-
Noise indoor *
7
dB-A (H/M/L)
36 / 31 / 28
-
-
-
Power Level dB
51 / 46 / 43
-
-
-
Noise outdoor
dB-A (H/L)
-
47 / -
-
-
Power Level dB
-
64 / -
-
-
H
E
A
T
I
N
G
Capacity
kW
6.0
6.0
6.0
-
-
-
1.8
7.0
BTU/h
20500
20500
20500
-
-
-
6100
23900
Current
A
-
-
-
6.20
5.95
5.70
-
-
Input power
W
-
-
-
-
-
-
-
-
TOTAL W
-
1.340k
1.340k
1.340k
0.240k
2.200k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
4.48
4.48 / A
4.48
7.50
3.18
ErP
*
6
Pdesign at -10°C
kW
-
-
-
-
4.6
-
-
-
Tbivalent
°C
-
-
-
-
-10
-
-
-
SCOP
(W/W)
-
-
-
-
4.9
-
-
-
Annual consumption
kWh
-
-
-
-
1314
-
-
-
elbu(-10°C)
kW
-
-
-
-
0.00
-
-
-
Class
-
-
-
-
A++
-
-
-
Power factor
%
-
-
-
98
98
98
-
-
Noise indoor *
7
dB-A (H/M/L)
36 / 31 / 28
-
-
-
Power Level dB
51 / 46 / 43
-
-
-
Noise outdoor
dB-A (H/L)
-
48 / -
-
-
Power Level dB
-
65 / -
-
-
LOW TEMP Total capacity(kW) / Input power(W) / COP
-
-
-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
-
-
-
-
-
Max Current(A) / Max Input power(W)
-
-
-
13.1 / 2.60k
13.1 / 2.65k
13.1 / 2.70k
-
Starting current(A) (Cooling/Heating)
-
-
-
7.45 / 6.20
7.15 / 5.95
6.85 / 5.70
-
Comp output(W)
-
1.70k
1.70k
1.70k
-
Time Delay fuse max size(A)
-
20
-
Network Impedance(ΩMAX.)
-
-
-
Fan motor output (Indoor/Outdoor) W
60
40
-
Moisture removal volume
L/h
1.7 (1.7 ×1)
-
-
External static pressure
Pa
-
-
-
Indoor
Air flow
*
7
Cooling
m³/min (H/M/L)
21.0 / 16.0 / 13.0
-
-
-
Heating
m³/min (H/M/L)
21.0 / 16.0 / 13.0
-
-
-
Outdoor
Air flow
Cooling
m³/min
-
42.6
-
-
Heating
m³/min
-
41.5
-
-
Refrigerant type / amount(ship) k
g
/ amount(max) k
g
-
R32
1.150
1.490
-
F-Gas
GWP /
CO2eq (ton) (PRECHARGED AMOUNT) /
CO2eq (ton) (MAXIMUM CHARGED AMOUNT)
-
675
0.78
1.01
-
Product dimension
Height
mm
256
695
-
Width
mm
840
875
-
Depth
mm
840
320
-
Product dimension (Panel)
H×W×D
mm
33.5 × 950 × 950
-
-
Packing dimension
Height
mm
302
761
-
Width
mm
898
1049
-
Depth
mm
898
460
-
Weight
(NET)
k
g
20
42
-
(GROSS)
k
g
26
46
-
Panel (NET)
k
g
5
-
-
Layers limit (actually)
11 (12)
3 (4)
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-10°C ~ 43°C
-
Heat (DBT)
16°C ~ 30°C
-15°C ~ 24°C
-
Max Working Pressure HP/LP MPa
4.15 / 2.55
-
P
I
P
I
N
G
Pipe port diameter mm (inch)
(Liquid)Ø9.52(3/8) (Gas)Ø15.88(5/8)
(Liquid)Ø6.35(1/4) (Gas)Ø12.7(1/2)
-
Pipe diameter mm (inch)
(Liquid)Ø6.35(1/4) (Gas)Ø12.7(1/2) *Connect the gas socket tube(Ø15.88-Ø12.7) to the gas tubing side indoor unit
*Connect the liquid socket tube(Ø9.52-Ø6.35) to the liquid tubing side indoor unit
-
Connecting method
flared type
flared type
-
Standard length m
5 m
-
Pipe length range m
3 ~ 30 m
-
Indoor unit & Outdoor unit height difference m
15 m(OD located lower) / 15 m(OD located higher)
-
Add gas amount
g
/m
15
g
/m
-
Pipe length for additional gas m
7.5 m
-
* In the case of nanoe X OFF
*1 In case it is necessary to indicate the air flow volume in (l/s), the value in (m³/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2
If the EUROVENT Certified models can be operated under the "extra-low" temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage 230V shall be used.
*3 Network Impedance shall be applicable for EUROPE and CHINA models.
*4 The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5 EER and COP classification is at 230V(400V) only in accordance with EU directive 2002/31/EC.
*6
SEER and SCOP classification is at 230V(400V) only in accordance with EN-14825. For heating, SCOP indicates the value of only Average heating season, Other fiche data indicates in an attached sheet.
*7 H : High at setting 5 stage (Level 5), M : Middle at setting 5 stage (Level 3), L : Low at setting 5 stage (Level 1)
SM830283-00_欧州向け R32シングル36-71形TD&SM.indb 3
20/01/30 10:24:31
Содержание S-3650PF3E
Страница 20: ...19 MEMO SM830283 00_欧州向け R32シングル36 71形TD SM indb 19 2020 01 29 21 46 03 ...
Страница 178: ... MEMO 1 13 5 SM830283 00_欧州向け R32シングル36 71形TD SM indb 5 20 01 30 10 26 09 ...
Страница 198: ... MEMO 2 4 1 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 2020 01 29 19 52 20 ...
Страница 204: ... MEMO 3 2 1 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 20 01 28 11 25 46 ...
Страница 270: ... MEMO 5 4 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 2020 01 29 21 17 57 ...
Страница 272: ... MEMO 6 1 SM830283 00_欧州向け R32シングル36 71形TD SM indb 1 20 01 20 10 15 08 ...
Страница 294: ... MEMO 7 21 SM830283 00_欧州向け R32シングル36 71形TD SM indb 21 20 01 28 11 22 25 ...
Страница 321: ...202001 SM830283 00_欧州向け R32シングル36 71形TD SM indb 1 20 01 23 9 32 11 ...