1
1-11-2-1-15
(E) When outdoor units are installed in rows, such as on a rooftop (L < H)
(1) One outdoor unit installed in each row
a
b
d
c
L
H
a
500 mm or more
b
300 mm or more
c
1,000 mm or more
d
50 mm or more
(2) Two or more units installed side by side.
b
A
c
a
d
e
H
L
a
1,000 mm or more
b
400 mm or more
c
2,000 mm or more
d
250 mm or more
e
250 mm or more
The dimensional relationship between H, A, and L is as
shown in the following table.
Unit: mm
A
0
5
1
H
<
L
H < L Installation is not allowed.
The values described above are the least space to
optimize application performance.
If any service area is needed for service according to
field circumstance, obtain enough service space.
• The above mentioned distance is required for optimal unit performance.
Allow as much space as possible in order to obtain the best performance from the units.
SM830283-00_欧州向け R32シングル36-71形TD&SM.indb 15
20/01/30 10:26:02
Содержание S-3650PF3E
Страница 20: ...19 MEMO SM830283 00_欧州向け R32シングル36 71形TD SM indb 19 2020 01 29 21 46 03 ...
Страница 178: ... MEMO 1 13 5 SM830283 00_欧州向け R32シングル36 71形TD SM indb 5 20 01 30 10 26 09 ...
Страница 198: ... MEMO 2 4 1 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 2020 01 29 19 52 20 ...
Страница 204: ... MEMO 3 2 1 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 20 01 28 11 25 46 ...
Страница 270: ... MEMO 5 4 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 2020 01 29 21 17 57 ...
Страница 272: ... MEMO 6 1 SM830283 00_欧州向け R32シングル36 71形TD SM indb 1 20 01 20 10 15 08 ...
Страница 294: ... MEMO 7 21 SM830283 00_欧州向け R32シングル36 71形TD SM indb 21 20 01 28 11 22 25 ...
Страница 321: ...202001 SM830283 00_欧州向け R32シングル36 71形TD SM indb 1 20 01 23 9 32 11 ...