1
1-9-1
1
1-260
1-9. Intaking Fresh Air of 4-Way cassette Type
Precautions Regarding External Air Intake
1-9-1.
(1) Ventilation Load
Ensure that the design of the air-conditioner takes air-conditioning loads into consideration when external air intake is
involved.
(2) Restrictions on External Air Intake
Ensure that the design conforms to the restrictions on air intake volume stipulated in accordance with the model of
the indoor unit and the intake method. Consideration must also be taken to mixed air content listed in (3) below
without fail.
* If the air intake volume does not satisfy the required ventilation volume, air must be fed into the room separately with
the use of a total heat exchanger or a fresh air processing air-conditioner, etc.
(3) Mixed Air
The amount of external air intake must be set within the scope of the unit’s usage conditions when external air and
internal air is mixed together. This is especially important in the following cases, in which it is necessary to either
feed external air into the room after it has been processed or reduce the amount of external air that is fed in.
1
When the external dew-point temperature is greater than the dry-bulb temperature of the air sucked into the unit
Ensure that processing is performed so that the external dew-point temperature is lower than the temperature of
the air sucked into the unit to prevent the risk of condensation building up.
2
In the case of low external temperatures
There are cases in which the temperature of mixed air is lower than the operating range of the unit if excessive
amounts of external air intake are used when the external temperature is low.
This problem is to be solved by either feeding external air into the room after it has been processed or reducing
the amount of external air that is fed in.
3
When used in combination with humidifiers
External air must always be processed when the external air temperature reaches freezing point to prevent the
risk of the humidifier freezing.
(4) Arranging Ducts and Filters in the Field
External air intake ducting must be arranged in the field.
External air filters must also be installed without fail in order to
prevent the intake of dust and grit.
(5) Thermal Insulation for Ducts
Ensure that all external air intake ducting is heat-insulated
without fail. Failure to observe this may result in the build-up
of condensation.
(6) External Air Intake Coupling
Ensure that the design for external air intake is coupled with
the fan blower operations of the indoor unit.
There are cases in which the dust that accumulates in the
filter is blown into the room if the external air is fed from the
filter. There are also cases in which the noise of external air
being fed into the room can be heard from the indoor unit if
external air is forcibly fed when the booster fan or other
components on the indoor unit are not operating.
(7) Booster Fan Selection
Select the booster fan in accordance with the resistance of
the external air intake duct (diagram on the pressure loss
characteristics of the air flow volume for flexible cylindrical
ducts) and the resistance prevalent inside the unit (external
air intake volume & resistance within unit / operation noise
characteristics).
Regarding the installation direction of the external air intake
duct, refer to the Installation Instructions provided with the
external air intake duct.
(8) Attaching the External Air Intake Flange
ø100
ø150
ø125
Airflow (m
3
/h)
Pressure Loss (Pa)/Mete
r
Flexible Cylindrical Duct
Air Flow Volume for Flexible Cylindrical
Duct-Pressure Loss
30 50
100
200
400 500
300
30
20
10
0.8
0.6
0.4
0.2
0.1
6
4
2
1
1-9. Fresh Air Intake
SM830283-00_欧州向け R32シングル36-71形TD&SM.indb 1
20/01/30 10:24:51
Содержание S-3650PF3E
Страница 20: ...19 MEMO SM830283 00_欧州向け R32シングル36 71形TD SM indb 19 2020 01 29 21 46 03 ...
Страница 178: ... MEMO 1 13 5 SM830283 00_欧州向け R32シングル36 71形TD SM indb 5 20 01 30 10 26 09 ...
Страница 198: ... MEMO 2 4 1 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 2020 01 29 19 52 20 ...
Страница 204: ... MEMO 3 2 1 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 20 01 28 11 25 46 ...
Страница 270: ... MEMO 5 4 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 2020 01 29 21 17 57 ...
Страница 272: ... MEMO 6 1 SM830283 00_欧州向け R32シングル36 71形TD SM indb 1 20 01 20 10 15 08 ...
Страница 294: ... MEMO 7 21 SM830283 00_欧州向け R32シングル36 71形TD SM indb 21 20 01 28 11 22 25 ...
Страница 321: ...202001 SM830283 00_欧州向け R32シングル36 71形TD SM indb 1 20 01 23 9 32 11 ...