2
2
2-3-1-2
(1)
2-3-1-4. Test Run Using the Remote Controller
CZ-RTC5B (High-spec wired remote controller)
Keep pressing the
,
and
buttons
simultaneously for 4 or more seconds.
The “Maintenance func” screen appears on the LCD display.
Maintenance func
Sel.
20:30 (THU)
1. Outdoor unit error data
2. Service contact
3. RC setting mode
4. Test run
Page [
] Confirm
Change the display from “OFF” to “ON” by pressing the
or
button. Then press the
button.
[
] Confirm
Test run
Change
20:30 (THU)
Test run
ON
20:30 (THU)
[ ] START
CZ-RTC5B
If you wish to see the next screen instantly, press the
(2) Press the
or button to see each menu.
or
button.
Select “4. Test run” on the LCD display and press the
button.
Maintenance func
Sel.
Page [
] Confirm
20:30 (THU)
1. Outdoor unit error data
2. Service contact
3. RC setting mode
4. Test run
CZ-RTC4 (Timer remote controller)
Press the remote controller
(1)
button for 4 seconds or longer.
Then press the
button.
“
” appears on the LCD display while the test run is in progress.
The temperature cannot be adjusted when in Test Run mode.
(This mode places a heavy load on the machines. Therefore use it
only when performing the test run.)
operation modes.
(2) The test run can be performed using the HEAT, COOL, or FAN
NOTE
The outdoor units will not operate for approximately 3 minutes after
the power is turned ON and after operation is stopped.
(1)
(1)
(4)
(3) If correct operation is not possible, a code is displayed on the remote
controller LCD display.(Regarding the alarm contents,
see section “2-3-1-5. Contents of Remote Controller Switch Alarm Display”)
(4) After the test run is completed, press the
button again.
Check that “
” disappears from the LCD display.
(To prevent continuous test runs, this remote controller includes a timer function that cancels the test run
after 60 minutes.)
* If the test run is performed using the wired remote controller, operation is possible even if the cassette-type
ceiling panel has not been installed. (“P09” display does not occur.)
CZ-RTC4
(3) Press the
on the LCD display.
button. “TEST” will be displayed
[ ] START
20:30 (THU)
TEST
(4) Press the
button. Test run will be started.
Test run setting mode screen appears on the LCD
display.
FAN SPEED
FLAP
20:30 (THU)
COOL
DE
TEST
MO
FAN SPEED
FLAP
20:30 (THU)
COOL
DE
TEST
MO
Type U3
Type F3
SM830283-00_欧州向け R32シングル36-71形TD&SM.indb 2
2020/01/29 19:52:15
Содержание S-3650PF3E
Страница 20: ...19 MEMO SM830283 00_欧州向け R32シングル36 71形TD SM indb 19 2020 01 29 21 46 03 ...
Страница 178: ... MEMO 1 13 5 SM830283 00_欧州向け R32シングル36 71形TD SM indb 5 20 01 30 10 26 09 ...
Страница 198: ... MEMO 2 4 1 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 2020 01 29 19 52 20 ...
Страница 204: ... MEMO 3 2 1 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 20 01 28 11 25 46 ...
Страница 270: ... MEMO 5 4 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 2020 01 29 21 17 57 ...
Страница 272: ... MEMO 6 1 SM830283 00_欧州向け R32シングル36 71形TD SM indb 1 20 01 20 10 15 08 ...
Страница 294: ... MEMO 7 21 SM830283 00_欧州向け R32シングル36 71形TD SM indb 21 20 01 28 11 22 25 ...
Страница 321: ...202001 SM830283 00_欧州向け R32シングル36 71形TD SM indb 1 20 01 23 9 32 11 ...