10-29
Param-
eter
No.
Ref-
er-
ence
page
Changes
during
opera-
tion
Default
setting
Unit
of
set-
ting
Set-
ting
range
Description
Name
Regis-
ter No.
n166
01A6
Input open--
phase detec-
tion level (see
note 1)
Sets the main circuit DC voltage fluc-
tuation level, as a percentage, for de-
tecting an input open phase.
200-V-class Inverters: Set 400 V as
100%.
400-V-class Inverters: Set 800 V as
100%.
If “0” is set, the input open-phase
detection function will be disabled.
Recommended setting: 7 (%)
Note
Applicable for software version
No. 010024 or later.
0 to
100
1%
0
No
6--50
n167
01A7
Input open--
phase detec-
tion time (see
note 1)
Sets the input open-phase detection
time in units of seconds.
If “0” is set, the input open-phase
detection function will be disabled.
Recommended setting: 10 (s)
Note
Applicable for software version
No. 010024 or later.
0 to
255
1s
0
No
6--50
n168
01A8
Output open--
phase detec-
tion level (see
note 1)
Sets as a percentage the current for
detecting an output open phase, tak-
ing the Inverter’s rated output current
as 100%.
If “0” is set, the output open-phase
detection function will be disabled.
Recommended setting: 5 (%)
Note
Applicable for software version
No. 010024 or later.
0 to
100
1%
0
No
6--51
n169
01A9
Output open--
phase detec-
tion time (see
note 1)
Sets the output open-phase detection
time in units of seconds.
If “0” is set, the output open-phase
detection function will be disabled.
Recommended setting: 0.2 (s)
Note
Applicable for software version
No. 010024 or later.
0.0 to
2.0
0.1s
0.0
No
6--51
n170
to
n172
---
Not used
---
---
---
---
---
---
n173
01AD
DC injection
P gain
Adjust the response of the DC injec-
tion with the proportional gain (P).
Note
Applicable for software version
No. 010024 or later.
1 to
999
1
(=0.001)
83
(=0.083)
n174
01AE
DC injection I
time
Adjust the response of the DC injec-
tion with the integral time (I).
Note
Applicable for software version
No. 010024 or later.
1 to
250
1
(=4ms)
25
(=100ms)
List of Parameters
Chapter 10
Summary of Contents for SYSDRIVE 3G3MV A2002
Page 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Page 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Page 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 311: ...Chapter 10 List of Parameters 10...
Page 342: ...Chapter 11 Using the Inverter for a Motor 11...
Page 348: ...Appendix A Standard Models...