10-13
19
Emergency
stop fault
(NO)
The Inverter stops
according to the setting
in n005 for interruption
mode selection with
the emergency stop
input turned ON.
20
Emergency
stop alarm
(NO)
input turned ON.
NO: Emergency stop
with the contact
closed.
NC: Emergency stop
with the contact
21
Emergency
stop fault
(NC)
with the contact
opened.
Fault: Fault output is
ON and reset with
RESET input. Alarm
output is ON (no reset
required).
22
Emergency
stop alarm
(NC)
output is ON (no reset
required).
“STP” is displayed (lit
with fault input ON and
flashes with alarm
input ON)
23
PID control
cancel
ON: PID control dis-
abled.
24
PID control
integral
reset
ON: Integral value
reset.
25
PID control
integral
hold
ON: Keeps integral
value on hold.
26
(see
note)
Inverter
overheating
warning
ON: Displays inverter
overheating warning
(oH3)
34
Up or down
command
Up or down command
(set in n56 only)
By setting n56 to 34,
the set value in n55 is
ignored and the follow-
ing setting are forcibly
made.
S6: Up command
S7: Down command
35
Self-diag-
nostic test
ON: RS-422/485 com-
munications self-diag-
nostic test (set in n056
only)
Note
Available for 5.5kW and 7.5kW Inverters only.
List of Parameters
Chapter 10
Summary of Contents for SYSDRIVE 3G3MV A2002
Page 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Page 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Page 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 311: ...Chapter 10 List of Parameters 10...
Page 342: ...Chapter 11 Using the Inverter for a Motor 11...
Page 348: ...Appendix A Standard Models...