5-42
Value
Description
4
Output power (Reference: 10-V output at power equivalent to max. applicable
motor capacity and 0-V output during regenerative operation).
5
Output voltage (Reference: 10-V output at 200 VAC for 200-V models and
400 VAC for 400-V models)
Note
Output power cannot be monitored in vector control mode
n067
Multi-function Analog Out-
put Gain
Register
0143
Hex
Changes during
operation
Yes
Setting
range
0.00 to 2.00
Unit of
setting
0.01
Default setting
1.00
Note 1.
Refer to the above information on the set values in n066 and set the multiplica-
tion rate based on the reference value. For example, if 5-V output is desired at
maximum output frequency (with n066 set to 0), set n067 to 0.50.
Note 2.
The multi-function analog output terminals (AM and AC) have a maximum out-
put of 10 V.
5-11-2 Setting the Pulse Monitor Output (n065 and n150)
·
By setting n065 for multi-function analog output type selection to 1 for pulse train out-
put, monitoring pulse output frequency signals is possible through the multi-function
analog output terminals.
·
The relationship between the output frequency and pulse train output frequency is set
in n150 for multi-function analog output, pulse train frequency selection.
n065
Multi-function Analog Out-
put Type Selection
Register
0141
Hex
Changes during
operation
No
Setting
range
0, 1
Unit of
setting
1
Default setting
0
Set Values
Value
Description
0
Analog voltage output (with monitoring item set in n066)
1
Pulse train output (according to output frequency set in n150)
n150
Multi-function Analog
Output, Pulse Train
Frequency Selection
Register
0197
Hex
Changes during
operation
No
Setting
range
0, 1, 6, 12, 24, and 36
Unit of
setting
1
Default setting
0
Basic Operation
Chapter 5
Summary of Contents for SYSDRIVE 3G3MV A2002
Page 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Page 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Page 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 311: ...Chapter 10 List of Parameters 10...
Page 342: ...Chapter 11 Using the Inverter for a Motor 11...
Page 348: ...Appendix A Standard Models...