2-45
H
Conforming to LVD
·
Always connect the Inverter and power supply via a molded case circuit breaker
(MCCB) suitable to the Inverter for protecting the Inverter from damage that may result
from short-circuiting.
·
Use one MCCB per Inverter.
·
Select a suitable MCCB from the following table.
200-V Models
Inverter
MCCB (Mitsubishi Electric)
Model 3G3MV-
Type
Rated current (A)
A2001
NF30
5
A2002
NF30
5
A2004
5
A2007
10
A2015
20
A2022
20
A2040
30
A2055
50
A2075
60
AB001
NF30
5
AB002
NF30
5
AB004
10
AB007
20
AB015
20
AB022
40
AB040
50
400-V Models
Inverter
MCCB (Mitsubishi Electric)
Model 3G3MV-
Type
Rated current (A)
A4002
NF30
5
A4004
NF30
5
A4007
5
A4015
10
A4022
10
A4030
20
A4040
20
A4055
30
A4075
30
Design
Chapter 2
Summary of Contents for SYSDRIVE 3G3MV A2002
Page 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Page 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Page 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 311: ...Chapter 10 List of Parameters 10...
Page 342: ...Chapter 11 Using the Inverter for a Motor 11...
Page 348: ...Appendix A Standard Models...