5-26
n074
Pulse Train Frequency
Reference Gain
Register
014A
Hex
Changes during
operation
Yes
Setting
range
--255 to 255
Unit of
setting
1%
Default setting
100
n075
Pulse Train Frequency
Reference Bias
Register
014B
Hex
Changes during
operation
Yes
Setting
range
--100 to 100
Unit of
setting
1%
Default setting
0
Frequency
reference (Hz)
Pulse train input frequency (Hz)
n011: Maximum frequency
H
Pulse Train Frequency Reference Input Filter Constant (n076)
·
This parameter can be used to set a primary-delay digital filter for pulse train frequency
reference input.
·
This parameter setting is effective for smooth operation of the Inverter if the pulse train
input signal changes too rapidly or the signal is interfered with by noise.
·
The larger the set value is, the lower the response will be.
n076
Pulse Train Frequency
Reference Input Filter
Constant
Register
014C
Hex
Changes during
operation
No
Setting
range
0.00 to 2.00
Unit of
setting
0.01 s
Default setting
0.10
Basic Operation
Chapter 5
Summary of Contents for SYSDRIVE 3G3MV A2002
Page 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Page 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Page 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 311: ...Chapter 10 List of Parameters 10...
Page 342: ...Chapter 11 Using the Inverter for a Motor 11...
Page 348: ...Appendix A Standard Models...