6-38
n105
Torque Compensation Core
Loss
Register
0168
Hex
Changes during
operation
No
Setting
range
0.0 to 6,550 (W)
Unit of
setting
0.1 W
(see
note 1)
Default setting
See
note 2
Note 1.
The value will be set in 0.1-W increments if the loss is less than 1,000 W and
1-W increments if the loss is 1,000 W or over.
Note 2.
The default setting varies with the capacity of the Inverter model.
Set Values
·
Set this value to the core loss of the motor in used.
·
This parameter is valid in V/f control mode only.
·
Normally, the default setting does not need to be changed.
·
Set the value if the capacity of the motor does not coincide with the maximum applica-
ble motor capacity of the Inverter.