7-22
7-5 Setting the Communications Data
The following description provides information on how to convert the regis-
ter data (such as monitor value or parameter set value data) in the commu-
nications data block of the message data (such as DSR and response
data).
H
Converting the Register Data
·
The data in each register is sent as 2-byte data.
·
The data in each register is processed under the following rules and sent in hexadeci-
mal.
D
The data is converted to a hexadecimal value based on the minimum
unit of setting of each register as 1.
If the frequency reference is 60 Hz and the minimum unit of setting will
be 0.01 Hz, the data will be converted as follows:
60 (Hz)/0.01 (Hz) = 6000 = 1770 Hex
Note 1.
The minimum unit of setting of each parameter is indicated whenever the
parameter is explained in this manual and in
Section 10 List of Parameters
. For
registers other than those of parameters, refer to
7-6 Register Number Alloca-
tions in Details
.
Note 2.
The minimum unit of setting of frequency reference data or frequency monitor
data is determined by n152 (register 0198 Hex: RS-422/485 communications
frequency reference/monitor unit selection). The unit of setting of each of the
three registers below is determined by the set value in n152. For the units of
setting of these constants, refer to the
List of Parameters
. The set value in n152
has nothing to do with frequency data items set as parameter constants (e.g.,
frequency references 1 through 16, inching frequency reference, maximum fre-
quency, minimum output frequency, jump frequency).
S
Monitor Items
Register 0023: Frequency reference monitor
Register 0024: Output frequency monitor
S
Communications-dedicated Register
Register 0002: Frequency reference
In spite of the set value in n152, however, set the maximum frequency to 3000 when
the frequency reference is executed with a broadcast message. In this case, the
Inverter rounds off any value less than 0.01 Hz.
Communications
Chapter 7
Summary of Contents for SYSDRIVE 3G3MV A2002
Page 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Page 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Page 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 311: ...Chapter 10 List of Parameters 10...
Page 342: ...Chapter 11 Using the Inverter for a Motor 11...
Page 348: ...Appendix A Standard Models...