7-44
·
The following memory allocations are made in the above example.
SYSMAC CS1-series or C200HX/HG/HE
Programmable Controllers
Communications
Board
3G3MV
C: Control data (see note)
Communica-
tions port
1: Port A
2: Port B
Sequence No.
000 to 999 (BCD)
Data
No. of data items send in accordance with PMCR
instruction (000A)
No. of Slaves (0003)
First Slave address (0001)
RUN command to Slave 1
Frequency reference to Slave 1
Second Slave address (0002)
RUN command to Slave 2
Frequency reference to Slave 2
Third Slave address (0003)
RUN command to Slave 3
Frequency reference to Slave 3
No. of data items received in accordance with
PMCR instruction (0003)
Slave 1 Inverter status
Slave 2 Inverter status
Slave 3 Inverter status
Note
Control data on the SYSMAC
C200HX/HG/HE is indicated.
The SYSMAC CS1 Series uses
different control data.
P
ro
to
co
lm
ac
ro
fun
ct
ion
H
Creating a New Project and Protocol
1. Select
New
from the
File
in the Menu Bar or click on the
New
icon with the left button
of the mouse to create a new project.
2. If CX-Protocol is used, set the PC name, PC model, and network type according to
the actual conditions.
Note 1.
The network type refers to the type of the network connected to the Support
Software and it does not refer to the communications configuration between the
Programmable Controller and the 3G3MV Inverter.
Note 2.
The above settings will not be displayed if the Protocol Support Tool is used.
3. Double-click on
New Project
with the left button of the mouse to display
List of Pro-
tocols
.
4. Click on
List of Protocols
with the left button of the mouse and click on a blank
space with the right button of the mouse.
5. Select
New Protocol
.
Communications
Chapter 7
Summary of Contents for SYSDRIVE 3G3MV A2002
Page 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Page 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Page 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 311: ...Chapter 10 List of Parameters 10...
Page 342: ...Chapter 11 Using the Inverter for a Motor 11...
Page 348: ...Appendix A Standard Models...