6-34
·
If n115 is set to 1, the stall prevention level will be suppressed as shown below. When
using frequencies exceeding the maximum voltage frequency, set n 115 to 1.
Operation level
Automatic Suppression of Stall Prevention Level (n115 Set to 1)
Constant output range
Operating level: n094 x
(Max. voltage
frequency/output frequency)
Max. voltage frequency (FA)
Output frequency
40% of n094
n116
Stall Prevention
Acceleration/Deceleration
Time Setting
Register
0174
Hex
Changes during
operation
No
Setting
range
0, 1
Unit of
setting
1
Set Values
0
Set Values
Value
Description
0
Accelerates or decelerates at acceleration/deceleration time 1 or 2 presently
selected.
1
Accelerates or decelerates at acceleration/deceleration time 2 set in n021
and n022.
·
Select the acceleration/deceleration time with the stall prevention function operating
function enabled.
·
To accelerate or decelerate quicker or slower than normal, set 1 in n116 and the accel-
eration time in n021 (acceleration time 2) and deceleration time in n022 (deceleration
time 2) for stall prevention use.
Advanced Operation
Chapter 6
Summary of Contents for SYSDRIVE 3G3MV A2002
Page 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Page 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Page 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 311: ...Chapter 10 List of Parameters 10...
Page 342: ...Chapter 11 Using the Inverter for a Motor 11...
Page 348: ...Appendix A Standard Models...