6-17
6-3-5 Input Selection of PID Control Target Value and
Detection Value
·
The target value and detected value (feedback value) of PID control are set according
to n004 for frequency reference selection, n008 for local mode frequency reference
selection, and n164 PID feedback input block selection as shown in the following dia-
gram.
Make sure that the target value input and feedback value input do not overlap with
each other. Setting details are provided from the next page onward.
H
Input Selection of PID Control Target Value
Local/Remote
Multi-step speed
reference
FREQUENCY adjuster of the
Digital Operator
Frequency reference 1 (n024)
External terminal (0 to 10 V)
External terminal (4 to 20 mA)
External terminal (0 to 20 mA)
Pulse train input
Communications frequency reference
Multi-function analog input (0 to 10 V)
Multi-function analog input (4 to 20 mA)
FREQUENCY adjuster of the
Digital Operator
Frequency reference 1 (n024)
Frequency reference 2 (n025)
Frequency reference 3 (n026)
Frequency reference 4 (n027)
Frequency reference 16 (n127)
Inching frequency (n032)
Target value
H
Input Selection of PID Control Detection Value
Feedback value
External terminal (0 to 10 V)
External terminal (4 to 20 mA)
External terminal (0 to 20 mA)
Multi-function analog input (0 to 10 V)
Multi-function analog input (4 to 20 mA)
Pulse train input
Advanced Operation
Chapter 6
Summary of Contents for SYSDRIVE 3G3MV A2002
Page 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Page 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Page 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 311: ...Chapter 10 List of Parameters 10...
Page 342: ...Chapter 11 Using the Inverter for a Motor 11...
Page 348: ...Appendix A Standard Models...