6-11
Set Values
·
When the output frequency is constant for a certain period while the Inverter is in effec-
tive energy-saving control, the Inverter will be set to the primary level of energy-saving
control by n140 (energy-saving constant K2). Then the Inverter will be set to the sec-
ondary level (i.e., probe operation) for more efficient, energy-saving control. Set the
control voltage range of the Inverter in probe operation in parameter n144.
·
Set the upper limit of probe operation voltage in percentage based on the rated motor
voltage as 100%. Normally set the value to approximately 10%.
·
No probe operation will be available if the value is set to 0.
n145
Probe Operation Control
Voltage Step at 100%
Register
0191
Hex
Changes during
operation
No
Setting
range
0.1 to 10.0 (%)
Unit of
setting
0.1%
Default setting
0.5
n146
Probe Operation Control
Voltage Step at 5%
Register
0192
Hex
Changes during
operation
No
Setting
range
0.1 to 10.0 (%)
Unit of
setting
0.1%
Default setting
0.2
Set Values
·
Set the range of probe operation voltage in percentage based on the rated motor volt-
age as 100%.
·
Normally, the default setting does not need to be changed.
·
If the fluctuation of speed in probe operation is large, decrease the set value. If the
response of the Inverter in probe operation is slow, increase the set value.
Control voltage step (%)
Inverter output voltage (%)
n161
Power Detection Width for
Probe Operation Switching
Register
01A1
Hex
Changes during
operation
No
Setting
range
0 to 100 (%)
Unit of
setting
1%
Default setting
10
Set Values
·
Set this parameter to the detection width of power that sets the Inverter to probe opera-
tion. When the fluctuation of power is within the detection width, the Inverter will be in
probe operation.
Advanced Operation
Chapter 6
Summary of Contents for SYSDRIVE 3G3MV A2002
Page 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Page 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Page 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 311: ...Chapter 10 List of Parameters 10...
Page 342: ...Chapter 11 Using the Inverter for a Motor 11...
Page 348: ...Appendix A Standard Models...