10-9
Param-
eter
No.
Ref-
er-
ence
page
Changes
during
opera-
tion
Default
setting
Unit
of
set-
ting
Set-
ting
range
Description
Name
Regis-
ter No.
n038
0126
Motor protec-
tive time
Used to set the electric thermal char-
acteristics of the motor to be con-
nected in 1-minute increments.
Note
The default setting does not
require any changes in normal
operation.
Note
To set the parameter according
to the characteristics of the
motor, check with the motor
manufacturer the thermal time
constant and set the parameter
with some margin. In other
words, set the value slightly
shorter than the thermal time
constant.
Note
To detect motor overloading
quicker, reduce the set value,
provided that it does not cause
any application problems.
1 to 60 1 min 8
No
6-41
n039
0127
Cooling fan
operation
Used to operate the Cooling Fan of
the Inverter while the Inverter is
turned ON or only while the Inverter is
in operation.
0: Rotates only while RUN command
is input and for 1 minute after
Inverter stops operating
1: Rotates while Inverter is turned ON
Note
This parameter is available only
if the Inverter incorporates a
Cooling Fan.
Note
If the operation frequency of the
Inverter is low, the life of the fan
can be prolonged by setting the
parameter to 0.
0, 1
1
0
No
6-42
n040
0128
Direction for
motor rotation
0: CCW
1: CW
The motor output shaft rotates in the
counterclockwise (’0”) or in the clock-
wise (”1”) direction with a forward in-
verter reference.
Note
Applicable for software version
No. 010024 or later.
0, 1
1
0
List of Parameters
Chapter 10
Summary of Contents for SYSDRIVE 3G3MV A2002
Page 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Page 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Page 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 311: ...Chapter 10 List of Parameters 10...
Page 342: ...Chapter 11 Using the Inverter for a Motor 11...
Page 348: ...Appendix A Standard Models...