This section explains the basic settings required to operate and stop the
Inverter.
The settings of parameters described here will be sufficient for simple
Inverter operations.
First, make these basic settings, then skip to the explanations of those spe-
cial functions, even when your application requires special functions, such
as energy-saving control, PID control, stall prevention, carrier frequency
setting, overtorque detection, torque compensation, slip compensation.
Refer to
Chapter 6 Advanced Operation
.
5-1 Initial Settings
·
The following initial settings are required.
Parameter Write-prohibit Selection/Parameter Initialization (n001): Set n001 to 4 so
that n001 through n179 can be set or displayed.
Control Mode Selection (n002): Set to V/f or vector control mode according to the
application.
5-1-1 Setting the Parameter Write-prohibit
Selection/Parameter Initialization (n001)
·
Set n001 to 4 so that n001 through n179 can be set or displayed.
n001
Parameter Write-prohibit
Selection/Parameter Initialization
Register
0101
Hex
Changes during
operation
No
Setting
range
0 to 9
Unit of
setting
1
Default setting
1
Note
This parameter makes it possible to write-prohibit parameters, change the
parameter set or displayed range, or initialize all parameters to default values.
Basic Operation
Chapter 5
Summary of Contents for SYSDRIVE 3G3MV A2002
Page 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Page 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Page 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 311: ...Chapter 10 List of Parameters 10...
Page 342: ...Chapter 11 Using the Inverter for a Motor 11...
Page 348: ...Appendix A Standard Models...