![background image](http://html1.mh-extra.com/html/omron/sysdrive-3g3mv-a2002/sysdrive-3g3mv-a2002_user-manual_742836138.webp)
5-39
Value
Description
Function
3
Zero-speed
ON: Idling (at less than min. output frequency)
4
Frequency detection 1 ON: Output frequency
frequency detection level
(n095)
5
Frequency detection 2 ON: Output frequency
frequency detection level
(n095)
6
Overtorque being
monitored
(NO-contact output)
Output if any of the following parameter conditions is
satisfied.
·
Overtorque detection function selection 1 (n096)
·
Overtorque detection function selection 2 (n097)
7
Overtorque being
monitored
(NC-contact output)
·
Overtorque detection level (n098)
·
Overtorque detection time (n099)
Note
NO contact: ON with overtorque being detected;
NC contact: OFF with overtorque being detected
8
Undertorque detection
(NO)
Closed if undertorque is detected
9
Undertorque detection
(NC)
Open if undertorque is detected
10
Alarm output
ON: Alarm being detected (Nonfatal error being
detected)
11
Base block in
progress
ON: Base block in progress (in operation with power
output turned OFF)
12
RUN mode
ON: Local mode (with the Digital Operator)
13
Inverter ready
ON: Inverter ready to operate (with no fault detected)
14
Fault retry
ON: Fault retry (Inverter resetting with fault retry (n082)
not set to 0)
15
UV in progress
ON: Undervoltage being monitored (main circuit
undervoltage UV1 detected)
16
Rotating in reverse
direction
ON: Rotating in reverse direction
17
Speed search in
progress
ON: Speed search in progress
18
Communications
output
ON: Communications output (turns ON/OFF according
to 0009 Hex set from communications. Communications
setting = ON)
19
PID feedback loss
ON: PID feedback being lost (set detection method in
n136, n137, n138)
20
Frequency reference
is missing
Closed if frequency reference is missing.
21
Inverter overheating
pre-alarm OH3
Closed if inverter overheating pre-alarm is input. Digital
operator display is “OH3” (blinking)
Basic Operation
Chapter 5
Summary of Contents for SYSDRIVE 3G3MV A2002
Page 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Page 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Page 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 311: ...Chapter 10 List of Parameters 10...
Page 342: ...Chapter 11 Using the Inverter for a Motor 11...
Page 348: ...Appendix A Standard Models...