6-45
·
Values will be set in 0.01-Hz increments if the frequency is less than 100 Hz and 0.1-Hz
increments if the frequency is 100 Hz or over.
·
These values must satisfy the following condition.
n083
n084
n085
·
The value in n086 must be set for the jump width.
·
This function is disabled with n086 set to 0.0.
·
The operation of the Inverter within the dead bands is prohibited. While the Inverter is
in acceleration or deceleration control, however, the Inverter does not jump the bands
but changes the frequency smoothly.
Frequency Jump Function
Output
frequency
Reference
frequency
6-10-7
Accumulated Operating Time (n087, n088)
·
The accumulated operating time function is provided for 5.5- and 7.5-kW Inverters
only.
·
This function calculates and stores in memory the Inverter’s accumulated operating
time. The accumulated operating time that is saved can be checked (unit: 10h) by the
“accumulated operating time” (U--13) of the multi-function monitor (MNTR indicator).
·
Use this function in determining the maintenance schedule.
n087
Accumulated Operating
Time
Register
0157
Hex
Changes during
operation
No
Setting
range
0, 1
Unit of
setting
1
Default setting
0
Advanced Operation
Chapter 6
Summary of Contents for SYSDRIVE 3G3MV A2002
Page 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Page 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Page 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 311: ...Chapter 10 List of Parameters 10...
Page 342: ...Chapter 11 Using the Inverter for a Motor 11...
Page 348: ...Appendix A Standard Models...