5-30
5-8 Selecting the Reverse Rotation-prohibit
This parameter is used to specify whether to enable or disable the reverse
rotation command sent to the Inverter from the control circuit terminals or
Digital Operator.
The parameter should be set to “not accept” when the Inverter is applied to
systems that prohibit the reverse rotation of the Inverter.
H
Selecting the Reverse Rotation-prohibit (n006)
n006
Reverse Rotation-prohibit
Selection
Register
0106
Hex
Changes during
operation
No
Setting
range
0, 1
Unit of
setting
1
Default setting
0
Set Values
Value
Description
0
Accept
1
Not accept
Basic Operation
Chapter 5