![background image](http://html1.mh-extra.com/html/omron/sysdrive-3g3mv-a2002/sysdrive-3g3mv-a2002_user-manual_742836133.webp)
5-34
Value
Description
Function
16
Acceleration/Decel-
eration-prohibit com-
mand
ON: Acceleration/Deceleration is on hold (running at
parameter frequency)
17
Local or remote
selection
ON: Local mode (operated with the Digital Operator)
Note
After this setting is made, mode selection with the
Digital Operator is not possible.
18
Communications/Re-
mote selection
ON: RS422/485 Communications input is enabled.
Communications RUN command (0001 Hex) is enabled
together with frequency reference (0002 Hex).
19
Emergency stop fault
(NO)
The Inverter stops according to the setting in n005 for
interruption mode selection with the emergency stop
input turned ON.
n005 set to 0: Decelerates to stop at deceleration time
20
Emergency stop
alarm (NC)
n005 set to 0: Decelerates to stop at deceleration time
2 set in n022. n005 set to 1: Coasts to a stop.
Note
NO: Emergency stop with the digital input closed.
NC: Emergency stop with the digital input opened.
Note
Fault: Fault output is ON and reset with RESET
21
Emergency stop fault
(NO)
Note
Fault: Fault output is ON and reset with RESET
input.
Alarm: Alarm output is ON and automatically
restored when emergency stop input is cleared (no
22
Emergency stop
alarm (NC)
restored when emergency stop input is cleared (no
reset required).
Note
“STP” is displayed (lit with fault input ON and
flashes with alarm input ON)
23
PID control cancel
ON: PID control is disabled.
PID control set is disabled and the Inverter is in normal
operation according to the n003 and n004 settings.
24
PID control integral
reset
ON: Integral value is reset (cleared).
The integral value as a result of PID operation is
cleared when the Inverter is in PID control. The input
status of the Inverter continues with the integral function
disabled.
25
PID control integral
hold
ON: Integral value is kept on hold (fixed).
The integral value as a result of PID operation is kept
on hold with only the integral operation function
disabled when the Inverter is in PID control.
26 (See
note.)
Inverter overheating
warning oH3
ON: oH3 display (at the Operator); Inverter overheating
warning output ON (multi-function output).
Operation continues during input. When the input turns
OFF, the Operator display and multi-function output are
cleared.
Use for functions such as displaying the status of
external thermal relays.
Note
Set value 26 is available for 5.5- and 7.5-kW Inverters only
.
Basic Operation
Chapter 5
Summary of Contents for SYSDRIVE 3G3MV A2002
Page 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Page 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Page 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 311: ...Chapter 10 List of Parameters 10...
Page 342: ...Chapter 11 Using the Inverter for a Motor 11...
Page 348: ...Appendix A Standard Models...