Sauter Components 

AXM 117S: Motorised drive (with positioner) for unit valves 

How energy efficiency is improved 

Automatic valve adjustment and intelligent cut-out enable maximum energy efficiency. 

Areas of application  

Actuation of through and three-way unit valves in the VUL, BUL, VXL and BXL series. For controllers 

with continuous output in combination with intelligent unitary control systems. 

Features 

  Pushing force 120 N 

  Fits onto valve with M30 × 1.5 thread 

  Stepping motor with control and electronic cut-off 

  Version with control action A or B or adjustable 

  Maintenance-free gearbox 

  Suitable for retrofitting existing installations using an appropriate adaptor 

  Operating status control using integrated LED display 

Technical description 

  Two-part plastic housing, light grey (RAL7035) 

  Nickel-plated brass nut 

  Connecting cable, light grey 1.50 m long, 3 × 0.25 mm² 

  Running time for 4 mm stroke: 60 s 

  Installation position: vertical to horizontal, but not upside down 

 

 

Operation 

During commissioning (with valve fitted), the actuator moves to the two end positions and memorises 

the number of steps taken to do so. The 0...10 V control signal is then linearly assigned to this effec-

tive stroke. The motor activates the valve and switches off as soon as the stroke position concurs with 

the controller signal. In the end positions or in the event of an overload, the motor is switched off with-

in 2 minutes. If the control voltage has not changed for 2 hours (in the range 0...0,5 V), the motor – 

after approx. 2 hours  –  runs briefly to the end positions and, if necessary, corrects its position 

memory. A complete cycle is performed every 24 hours on the AXM117SF202 and F302 in order to 

prevent the plug from jamming. The LED lights up when power is applied to the drive, and flashes 

when the motor is running. 

 

 

Y07552

M

 

100 %

 0 V    Output signal y        10 V

B07650

0 %

Direc

tion 

of op

era

tion 2

Dir

ec

tio

n

of op

era

tion 1

 

Type 

Direction of 

operation

1)

 

Running 

time 

Stroke 

Thrust 

Power 

Weight 

 

 

 

mm 

 

kg 

 

AXM 117S F202

 

60 

120 

2)

 

24 V~ 

0,15 

 

AXM 117S F302 

60 

120 

2)

 

24 V~ 

0,15 

 

AXM 117S F402 

1 or 2 

3)

 

60 

120 

2)

 

24 V~ 

0,15 

 

 

 

Power supply 24 V~ 

±

 15%, 50...60 Hz

 

Ambient temperature 

–0...50 °C 

Power consumption on 

starting 

5 VA 

Ambient humidity 

< 75% rh 

 

 

Type of protection 

IP 40 (EN 60529) 

Control voltage 

0...10 V; Ri = 20 k

 

Protection class 

III (IEC 60730) 

Control voltage F402 

3)

 

0...10 V; 5,2...10 V; 0...4,8 V 

Wiring diagram 

A06147

 

Control current 

max. 0,5 mA 

Dimension drawing 

M06146

 

Max. operating temperature  100 °C at valve 

Fitting instructions 

MV 505456 

 

 

Accessories

 

 

0371235 001 

Adaptor for fitting to 

Oventrop

 valves (M30 

×

 1) 

 

0550393 001 

Adaptor Danfoss RA2000, 22 mm 

 

0371356 001 

Adaptor for fitting to 

Beulco

 or 

Tobler

 underfloor-heating distribution stations (M30 

×

 1) 

 

0550393 002 

Adaptor Danfoss RAVL, 26 mm 

 

0550393 003 

Adaptor Danfoss RAV, 34 mm 

 

0371361 001 

Adaptor for fitting to 

Herz

 valves, type Herz-TS’90 (M28 

×

 1,5) 

 

0371363 001 

Adaptor for fitting to 

Tour

 

& Andersson

 valves, type TA/RVT (M28 

×

 1,5) 

 

 

 

1) 

Direction of operation 1: rising 0…10V = drive retracts (VXL, VUL, BUL opens, BXL control passage closes). 
Direction of operation 2: rising 0…10V = drive extends (VXL, VUL, BUL closes, BXL control passage opens). 

2) 

Pushing force: min. 100 N, max. 150 N 

3) 

The direction of operation and the setting of the control voltage can be set using jumpers 

 

7155011003  07 