10-18
H
Function Group 3 (n080 through n0119)
Para
me-
ter
No.
Reg-
ister
No.
Name
Description
Set-
ting
range
Unit
of
set-
ting
Defaul
t set-
ting
Chan-
ges dur-
ing
opera-
tion
Ref-
er-
ence
page
n080
0150
Carrier fre-
quency
selection
Used to set the carrier frequency.
Note
The default setting does not need any
changes in normal operation.
Note
Refer to
6-4 Setting the Carrier Fre-
quency
for details.
1 to 4,
7 to 9
1
Varies
with
the
capac-
ity.
No
6-26
n081
0151
Momentary
power
interruption
compensa-
tion
Used to specify the processing that is per-
formed when a momentary power interruption
occurs.
0: Inverter stops operating
1: Inverter continues operating if power inter-
ruption is 0.5 s or less.
2: Inverter restarts when power is restored.
0 to 2 1
0
No
6-42
n082
0152
Number of
fault retries
Used set the number of times that reset and
restart are automatically attempted for the
Inverter when the Inverter has an overvoltage
fault or overcurrent fault.
0 to
10
1
0
No
6-43
n083
0153
Jump fre-
quency 1
Used to set the frequency jump function.
Output
frequency
0.0 to
400
0.01
Hz
0.00
No
6-44
n084
0154
Jump fre-
quency 2
0.0 to
400
0.01
Hz
0.00
No
6-44
n085
0155
Jump fre-
quency 3
Frequency
reference
0.0 to
400
0.01
Hz
0.00
No
6-44
n086
0156
Jump
width
Note
Set n083 to n085 to satisfy the following
condition.
n083
n084
n085
0.0 to
25.5
0.01
Hz
0.00
No
6-44
n087
0157
Accumu-
lated oper-
ating time
function
selection
(See note.)
Selects the operating status to be accumu-
lated.
0: Accumulate the time that the Inverter power
is ON (i.e., the time from when the power is
turned ON until it is shut OFF).
1: Accumulate Inverter execution time (i.e., the
time that forward or reverse signals are being
input).
0,1
1
0
No
6--45
n088
0158
Accumu-
lated oper-
ating time
(See note.)
Sets the initial value for the accumulated oper-
ating time, with 10 h as 1.
The accumulation begins from the set time.
The accumulated operating time’s monitor val-
ue (U-13) can be cleared to 0 by setting “0”
here.
0 to
6550
1 =
10H
0
No
6--46
Note
Accumulated operating time can be selected with 5.5kW and 7.5kW Inverters only.
List of Parameters
Chapter 10
Summary of Contents for SYSDRIVE 3G3MV A2002
Page 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Page 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Page 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 311: ...Chapter 10 List of Parameters 10...
Page 342: ...Chapter 11 Using the Inverter for a Motor 11...
Page 348: ...Appendix A Standard Models...