Setting the Motor Current Parameter
·
Run the Inverter in V/f control mode for trial operation. The control mode is not initial-
ized. Therefore, set n002 to 0 for V/f control. Set the motor current parameter in n036 in
order to prevent the motor from burning due to overloading.
H
Control Mode Setting
Parame-
ter
Register
Name
Description
Setting
range
Unit of
setting
Default
setting
Chan-
ges dur-
ing
opera-
tion
n002
0102
Control
mode
selection
Sets the control mode for the
Inverter.
0: V/f control mode
1: Vector control mode
Note
1.
The control mode
is not initialized
with n001 set-
tings.
Note
2.
There are param-
eters that are
changed accord-
ing to the set
value in n002. For
details, refer to
5-1-2 Setting the
Control Mode
(n002)
.
0, 1
1
0
No
Key sequence
Indicator
Display
example
Explanation
The parameter number is displayed.
Use the Increment or Decrement Key to
display “n002.”
Press the Enter Key to display the set value in
n002.
Use the Increment or Decrement key to set
n002 to 0 unless the value is already set to 0,
during which the display flashes.
Press the Enter Key so that the set value will
be entered and the data display will be lit.
In approximately
1 s.
The parameter number will be displayed again
in approximately 1 s.
Test Run
Chapter 4
Summary of Contents for SYSDRIVE 3G3MV A2002
Page 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Page 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Page 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 311: ...Chapter 10 List of Parameters 10...
Page 342: ...Chapter 11 Using the Inverter for a Motor 11...
Page 348: ...Appendix A Standard Models...