2-19
Communications method
Pin 1 setting
RS-422
Set to ON
RS-485
Set to ON only if the Unit is the end Slave.
120-
W
termination resistance (1/2 W)
Pin 1
D
Selecting Frequency Reference Input Method
·
By using pin 2 of SW2, voltage input or current input can be selected as the input
method for frequency reference. The default setting is for voltage input.
Parameter settings are required together with the selection of the frequency reference
input method.
Frequency reference input
method
Pin 2 setting
Frequency reference
selection (parameter n004)
Voltage input (default
setting)
V (OFF)
Set value 2
Current input
I (ON)
Set value 3 or 4
Note
Do not set pin 2 to ON for current input while voltage input is ON, otherwise the
resistor in the input circuit may burn out.
Design
Chapter 2