background image

Description

The in-back/out-back cooling kit fits the following drives in
E1h/E2h enclosures:

VLT

®

 HVAC Drive FC 102

VLT

®

 Refrigeration Drive FC 103

VLT

®

 AQUA Drive FC 202

VLT

®

 AutomationDrive FC 302

When the kit is installed, air flows into the lower back duct
and out through the upper back duct of the drive. See

Illustration 1.1

.

1

Top cover plate

4

Cooling channel

2

Enclosure

5

Airflow direction

3

Pedestal

6

Bottom cover plate

Illustration 1.1 Direction of Airflow with Kit Installed

Kit Part Numbers

Use these instructions with the following cooling kits.

Kit number

Kit description

176F6617

In-back/out-back cooling kit for E1h drive

176F6618

In-back/out-back cooling kit for E2h drive

Table 1.1 Part Numbers for Cooling Kits

Items Supplied

The in-back/out-back cooling kit contains the following items.

Item

Quantity

Top cover plate

1

Top gasket

1

Bottom cover plate

1

Bottom gasket

1

M5x14 screws

8–10

Table 1.2 Items Supplied in Cooling Kit

Safety Information

WARNING

DISCHARGE TIME

The drive contains DC-link capacitors, which can remain
charged even when the drive is not powered. High voltage
can be present even when the warning LED indicator lights
are off. Failure to wait 40 minutes after power has been
removed before performing service or repair work can result
in death or serious injury.

Stop the motor.

Disconnect AC mains and remote DC-link power
supplies, including battery back-ups, UPS, and DC-
link connections to other drives.

Disconnect or lock PM motor.

Wait 40 minutes for capacitors to discharge fully.

Before performing any service or repair work, use
an appropriate voltage measuring device to make
sure that the capacitors are fully discharged.

Installation Instructions

In-back/Out-back Cooling Kit for E1h/E2h Drives
VLT

®

 Series FC 102, FC 103, FC 202, and FC 302

Danfoss A/S © 09/2017 All rights reserved.

MI35D102

Summary of Contents for 176F6617

Page 1: ...tity Top cover plate 1 Top gasket 1 Bottom cover plate 1 Bottom gasket 1 M5x14 screws 8 10 Table 1 2 Items Supplied in Cooling Kit Safety Information WARNING DISCHARGE TIME The drive contains DC link...

Page 2: ...d Installation Instructions Installing the Top Cover Plate To install the top cover plate of the cooling kit use the following procedure See Illustration 1 2 1 Remove paper backing from the top gasket...

Page 3: ...between drive enclosure and top cover plate 6 Top surface of enclosure Illustration 1 2 Installation of Top Cover Plate Installation Instructions In back Out back Cooling Kit for E1h E2h Drives VLT Se...

Page 4: ...ws 3 Inside the pedestal position the bottom cover plate and gasket over the opening at the bottom of the cooling channel 4 Secure the bottom cover plate using the M5x14 screws T25 included with the k...

Page 5: ...the bottom cover plate and gasket over the opening at the lower end of the cooling channel 3 Secure the bottom cover plate using the M5x14 screws T25 provided with the kit Installation in E1h drives...

Page 6: ...0x30 fasteners See Illustration 1 6 Loosely tighten each bolt until all bolts are installed 3 Fasten each bolt securely and torque to 19 Nm 169 in lb 4 Torque the 2 M10 nuts at the rear of the enclosu...

Page 7: ...ew of E1h Drive E2h Drive Back Exterior Dimensions Illustration 1 8 Back View of E2h Drive Installation Instructions In back Out back Cooling Kit for E1h E2h Drives VLT Series FC 102 FC 103 FC 202 and...

Page 8: ...ucts already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed All trademarks in this material are property of the resp...

Reviews: