5-31
5-9 Selecting the Stopping Mode
This parameter is used to specify the stopping mode when the STOP com-
mand is input.
The Inverter either decelerates or coasts to a stop according to the stop-
ping mode selection.
H
Selecting the Stopping Mode (n005)
n005
Stopping Mode Selection
Register
0105
Hex
Changes during
operation
No
Setting
range
0, 1
Unit of
setting
1
Default setting
0
Set Values
Value
Description
0
Frequency deceleration stop (see note)
1
Free running
Note
The Inverter will decelerate to stop according to the setting in n020 for decelera-
tion time 1 if any of the n050 through n056 parameters for multi-function input is
not set to 11 for acceleration/deceleration time selection. If any one of the n050
through n056 multi-function input parameters is set to acceleration/deceleration
time selection, the Inverter will decelerate to stop according to the selected set-
ting of deceleration time when the STOP command is input.