3-12
·
The above procedure is possible provided that the Inverters have the same power sup-
ply specification and control mode (i.e., V/f or vector control). It is not possible to copy
parameters from a 200-V model to a 400-V model or from an Inverter that is in V/f con-
trol mode to another that is in vector control mode, for example.
Note 1.
The following parameter set values or output frequency on hold cannot be
copied.
n176: Parameter copy function selection
n177: Parameter read-prohibit selection
n178: Error log
n179: Software version
Note 2.
The following parameter set values cannot be copied if the Inverters are differ-
ent to each other in capacity.
n011 to n017: V/f setting
n036: Rated motor current
n080: Carrier frequency
n105: Torque compensation core loss
n106: Rated motor slip
n107: Motor wire-to-wire resistance
n108: Motor leakage inductance
n109: Torque compensation limit
n110: Motor no-load current
n140: Energy-saving control coefficient K2
n158: Motor code
Note 3.
Functions for 5.5/7.5kW Inverters cannot be copied to Inverters with different
capacities.
Preparing for Operation and Monitoring
Chapter 3
Summary of Contents for SYSDRIVE 3G3MV A2002
Page 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Page 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Page 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 311: ...Chapter 10 List of Parameters 10...
Page 342: ...Chapter 11 Using the Inverter for a Motor 11...
Page 348: ...Appendix A Standard Models...