8-12
Fault
display
Probable cause and remedy
Fault name and Meaning
cal
(flashing)
Communications standby
(CAL)
No normal DSR message has
been received during
RS-422/4895 communications.
The Inverter detects this alarm
only when RUN command
selection (n003) is set to 2 or
frequency reference selection
(n004) is set to 6. Until the
alarm is reset, no input other
than communications input will
be ignored.
·
A short-circuit, ground fault, or discon-
nection has occurred on the communica-
tions line.
®
Check and correct the line.
·
The termination resistance setting is
incorrect.
®
In the case of RS-422
communications, set pin 1 of SW2 of
all Inverters to ON. In the case of
RS-485 communications, set pin 1 of
SW2 of only the Inverter located at
each end of the network to ON.
·
Master’s program error.
®
Check the start of communications
and correct the program.
·
Communications circuit damage.
®
If the same error is detected as a
result of a self-diagnostic test, change
the Inverter.
Maintenance Operations
Chapter 8
Summary of Contents for SYSDRIVE 3G3MV A2002
Page 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Page 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Page 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 311: ...Chapter 10 List of Parameters 10...
Page 342: ...Chapter 11 Using the Inverter for a Motor 11...
Page 348: ...Appendix A Standard Models...