6-50
·
The following ON/OFF combinations of UP and DOWN commands are possible.
Command
Acceleration
Deceleration
Hold
Hold
S6 (UP command)
ON
OFF
OFF
ON
S7 (DOWN command)
OFF
ON
OFF
ON
·
With the UP/DOWN function used, the output frequency has the following restrictions
for upper and lower limits.
Upper limit: The maximum frequency in n011 or the frequency reference upper limit
in n033, whichever is smaller.
Lower limit: The minimum output frequency in n016 or frequency reference lower
limit in n034, whichever is smaller.
·
When the RUN command for forward or reverse rotation is input, the Inverter will start
operating at the lower limit regardless of whether the UP/DOWN command is input or
not.
·
When the UP/DOWN function and inching frequency command are both assigned to
multi-function inputs, an inching frequency command input will have the highest prior-
ity.
·
If n100 for UP/DOWN frequency storage is set to 1, the output frequency held by the
UP/DOWN function for 5 s or more will be stored in the memory. The output frequency
will be held by the UP/DOWN function when both UP and DOWN commands are ON or
OFF together.
6-10-10
Input Open-phase Detection (n166, n167)
·
The input open-phase detection function is provided for 5.5- and 7.5-kW Inverters only.
·
This function detects the occurrence of an input power supply open phase. The open
phase is detected by means of fluctuations in the main circuit DC voltage, enabling
detection of power supply voltage fluctuations and imbalances, decreasing values due
to ageing of the main circuit capacitor, and so on, in the same way.
·
If the fluctuations in the main circuit DC voltage exceed the input open-phase detection
level (n166), and persist at this level for longer than the input open-phase detection
time (n167), a main-circuit voltage fault (PF) will be detected.
n166
Input Open-phase Detection
Level
Register
01A6
Hex
Changes during
operation
No
Setting
range
0 to 100
Unit of
setting
1 %
Default setting
0
n167
Input Open-phase Detection
Time
Register
01A7
Hex
Changes during
operation
No
Setting
range
0 to 255
Unit of
setting
1 s
Default setting
0
Advanced Operation
Chapter 6
Summary of Contents for SYSDRIVE 3G3MV A2002
Page 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Page 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Page 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 311: ...Chapter 10 List of Parameters 10...
Page 342: ...Chapter 11 Using the Inverter for a Motor 11...
Page 348: ...Appendix A Standard Models...