![background image](http://html1.mh-extra.com/html/omron/sysdrive-3g3mv-a2002/sysdrive-3g3mv-a2002_user-manual_742836189.webp)
6-47
H
Frequency Detection
·
The multi-function outputs (n057 to n059) must be set to the following in order to issue
an output indicating that the frequency reference and the output frequency agree.
Set value: 2 for frequency agree
Frequency Detection Operation
Output
frequency
Detection width
±
2 Hz Reset width
±
4 Hz
Frequency reference
Time
Frequency
detection
Time
H
Frequency Detection Levels 1 and 2
·
The parameters in n057 to n059 for multi-function output must be set for frequency
detection output.
Set value: 4 for frequency detection level 1 (Output frequency
n095)
Set value: 5 for frequency detection level 2 (Output frequency
n095)
·
Set the frequency detection level in n095.
n095
Frequency Detection Level
Register
015F
Hex
Changes during
operation
No
Setting
range
0.00 to 400.0 (Hz)
Unit of
setting
0.01 Hz
Default setting
0.00
Set Values
·
Set the frequency to be detected.
Advanced Operation
Chapter 6
Summary of Contents for SYSDRIVE 3G3MV A2002
Page 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Page 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Page 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 311: ...Chapter 10 List of Parameters 10...
Page 342: ...Chapter 11 Using the Inverter for a Motor 11...
Page 348: ...Appendix A Standard Models...