10-17
Para
me-
ter
No.
Reg-
ister
No.
Name
Description
Set-
ting
range
Unit
of
set-
ting
Defaul
t set-
ting
Chan-
ges dur-
ing
opera-
tion
Ref-
er-
ence
page
n071
0147
Multi-func-
tion analog
current
input gain
Set the input characteristics of multi-function
analog current input.
Gain:Set the frequency of maximum analog
input (20 mA) in percentage based on the
maximum frequency as 100%.
--255
to 255
1%
100
Yes
NO TAG
n072
0148
Multi-func-
tion analog
current
input bias
input (20 mA) in percentage based on the
maximum frequency as 100%.
Bias: Set the frequency of minimum analog
input (0 V) in percentage based on the
maximum frequency as 100%.
--100
to 100
1%
0
Yes
NO TAG
n073
0149
Multi-func-
tion analog
current
input filter
time con-
stant
Set a primary delay digital filter for multi-function
analog current input.0.00 to 2.00
0.00
to
2.00
0.01 s 0.10
Yes
NO TAG
n074
014A Pulse train
frequency
reference
gain
Set the input characteristics of pulse train input.
Gain:Set the gain in percentage based on the
maximum frequency of the pulse train
input scale in n149 as 100%.
--255
to 255
1%
100
Yes
5-25
n075
014B Pulse train
frequency
reference
bias
input scale in n149 as 100%.
Bias: Set the bias in percentage for frequency
reference input at 0-Hz pulse train input
based on the maximum frequency as
100%.
--100
to 100
1%
0
Yes
5--24
n076
014C Pulse train
frequency
reference
input filter
time
constant
Sets the pulse train input’s primary-delay digital
filter for frequency reference.
0.00
to
2.00
0.01 s 0.10
Yes
5--25
n077
014D Multi--func-
tion analog
input termi-
nal func-
tion selec-
tion
Selects the function allocated to the multi-func-
tion analog input terminal.
0: Disable multi-function analog input function.
1: Auxiliary frequency reference
2: Frequency gain
3: Frequency bias
4: Output voltage bias
Note: When setting “3,” also set the standard
value for the bias in n079.
0 to 4 1
0
No
5--15
n078
014E Multi--func-
tion analog
input termi-
nal selec-
tion
Selects whether voltage input or current input is
to be used.
0: Enable multi-function analog voltage input
(and disable current input).
1: Enable multi-function analog current input
(and disable voltage input).
0,1
1
0
No
5--15
n079
014F Multi-func-
tion input
frequency
bias
When “3” is set for n077, set the standard value
for the bias as a percentage, taking the maxi-
mum frequency as 100%.
0 to
50
1%
10
No
5--15
List of Parameters
Chapter 10
Summary of Contents for SYSDRIVE 3G3MV A2002
Page 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Page 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Page 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 311: ...Chapter 10 List of Parameters 10...
Page 342: ...Chapter 11 Using the Inverter for a Motor 11...
Page 348: ...Appendix A Standard Models...