6-10
·
Normally, the default settings do not need to be changed. If the motor stalls or stops
because the internal constants of the motor are special, increase the set values by
approximately 5% to 10%.
Output voltage
lower limit (%)
Output frequency (Hz)
n159
Energy-saving Voltage
Upper Limit at 60-Hz Output
Register
019F
Hex
Changes during
operation
No
Setting
range
0 to 120 (%)
Unit of
setting
1%
Default setting
120
n160
Energy-saving Lower Limit
Voltage at 6-Hz Output
Register
01A0
Hex
Changes during
operation
No
Setting
range
0 to 25 (%)
Unit of
setting
1%
Default setting
16
Set Values
·
These parameters prevent the motor from over excitation due to voltage changes dur-
ing energy-saving control.
·
Set the upper limit of output voltage in percentage at each frequency based on the
rated motor voltage as 100%.
·
Normally, the default settings do not need to be changed.
Output voltage
upper limit (%)
Output frequency (Hz)
n144
Probe Operation Voltage
Limit
Register
0190
Hex
Changes during
operation
No
Setting
range
0 to 100 (%)
Unit of
setting
1%
Default setting
0
Advanced Operation
Chapter 6
Summary of Contents for SYSDRIVE 3G3MV A2002
Page 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Page 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Page 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 311: ...Chapter 10 List of Parameters 10...
Page 342: ...Chapter 11 Using the Inverter for a Motor 11...
Page 348: ...Appendix A Standard Models...