![background image](http://html1.mh-extra.com/html/omron/sysdrive-3g3mv-a2002/sysdrive-3g3mv-a2002_user-manual_742836174.webp)
6-32
n093
Stall Prevention Level
during Acceleration
Register
015D
Hex
Changes during
operation
No
Setting
range
30 to 200 (%)
Unit of
setting
1%
Set Values
170
Set Values
·
This function is used to stop accelerating the load if the output current exceeds the set
current value so that the Inverter will continue operating without stalling. The Inverter
accelerates the load while the output current is the same as or less than the set value.
·
Set the parameter as percentage based on the rated Inverter current as 100%.
·
The default setting does not need any changes in normal operation.
·
Decrease the set value if the capacity of the motor is smaller than that of the Inverter or
the motor stalls with the default value.
The set value is normally 2 or 3 times higher than the rated current of the motor. Set this
current as percentage based on the rated inverter current as 100%.
Stall Prevention during Acceleration
Output
current
n093 (stall prevention level
during acceleration)
Time
Output
frequency
The output frequency is controlled
so that the Inverter will not stall.
Time
n094
Stall Prevention Level
during Operation
Register
015E
Hex
Changes during
operation
No
Setting
range
30 to 200 (%)
Unit of
setting
1%
Default setting
160
Set Values
·
This function will decrease the output frequency if the output current exceeds the set
current value by a minimum of approximately 100 ms so that the Inverter will continue
operating without stalling. The Inverter will increase the output frequency to return to
the set frequency reference level when the output current is less than the set value.
Advanced Operation
Chapter 6
Summary of Contents for SYSDRIVE 3G3MV A2002
Page 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Page 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Page 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 311: ...Chapter 10 List of Parameters 10...
Page 342: ...Chapter 11 Using the Inverter for a Motor 11...
Page 348: ...Appendix A Standard Models...