6-52
Note 2.
If either n168 or n169 is set to 0, the output open-phase detection function will
be disabled.
Note 3.
If the applicable motor capacity is small in relation to the Inverter capacity, it
may cause errors in the output open-phase detection. To prevent this from oc-
curring, lower the output open-phase detection level to match the motor capac-
ity.
6-10-12
Fault Log (n178)
·
The 3G3MV stores information on the four most recent faults.
·
The latest record is displayed. By pressing the Increment Key, the previous record is
displayed. A maximum of four records can be checked.
·
The details of the information are the same as that obtained from the multi-function
monitor U-09.
n178
Fault Log
Register
01B2
Hex
Changes during
operation
---
Setting
range
---
Unit of
setting
---
Default setting
---
Note
The information is read only.
Display Example
D
Fault display
Fault code
D
No fault stored
Fault
generation
item
·
To clear the faultlog, set n001 for parameter write-prohibit selection/parameter initial-
ization to 6.
Advanced Operation
Chapter 6
Summary of Contents for SYSDRIVE 3G3MV A2002
Page 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Page 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Page 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 311: ...Chapter 10 List of Parameters 10...
Page 342: ...Chapter 11 Using the Inverter for a Motor 11...
Page 348: ...Appendix A Standard Models...